Table of Contents

1    Introduction
1.1  About this Document
1.2  Scope of the Document
1.3  Terms
2    CAN
2.1  CAN Overview
2.2  Hardware Restrictions
2.3  Simple Communication
2.3.1 Bootup and Heartbeat
2.3.2 Simple Read
2.3.3 Simple Write Prerequisities
2.3.4 Simple Write
2.3.5 Simple One Time Configuration
3    CANopen
3.1  Supported Communication Objects
3.2  EMCY Codes (CAN 1.01)
3.3  Error Status Bits
3.4  CAN Specific Errors
3.5  Parameter Description Sample
4    Parameter Description
4.1  Section CANopen
4.1.1 1000h - Device Type
4.1.2 1001h - Error Register
4.1.3 1003h - Pre-defined Error Field
4.1.4 1005h - COB-ID SYNC
4.1.5 1008h - Manufacturer Device Name
4.1.6 100Ah - Manufacturer Software Version
4.1.7 1010h - Store Parameter Field
4.1.8 1011h - Restore Default Parameters
4.1.9 1012h - COB-ID Time Stamp
4.1.10 1014h - COB-ID EMCY
4.1.11 1016h - Consumer Heartbeat Time
4.1.12 1017h - Producer Heartbeat Time
4.1.13 1018h - Identity Object
4.1.14 1200h - Server SDO Parameter 1
4.1.15 1400h - Receive PDO Communication Parameter 1
4.1.16 1600h - Receive PDO Mapping Parameter 1
4.1.17 1800h - Transmit PDO Communication Parameter 1
4.1.18 1801h - Transmit PDO Communication Parameter 2
4.1.19 1802h - Transmit MPDO Communication Parameter 3
4.1.20 1A00h - Transmit PDO Mapping Parameter 1
4.1.21 1A01h - Transmit PDO Mapping Parameter 2
4.1.22 1A02h - Transmit MPDO Mapping Parameter 3
4.1.23 1FA0h - Object Scanner List
4.2  Section Control
4.2.1 2000h - Setpoint (System)
4.2.2 2001h - Control Mode (System)
4.2.3 2002h - Command (System)
4.2.4 2008h - Bus Setpoint (System)
4.2.5 2009h - Bus Control Mode (System)
4.2.6 200Ah - Bus Command (System)
4.3  Section Status
4.3.1 2040h - Effective Capacity (System)
4.3.2 2041h - Effective Control Mode (System)
4.3.3 2042h - Effective Command (System)
4.3.4 2048h - Selected Setpoint (System)
4.3.5 2049h - Selected Control Mode (System)
4.3.6 204Ah - Selected Command (System)
4.3.7 2050h - Controller Status (System)
4.3.8 2052h - Operation Status (System)
4.3.9 2054h - Bus Status
4.3.10 2056h - Control Status
4.3.11 2058h - Ready for Operation (DP/MP)
4.3.12 205Ah - Pump is Operating (DP/MP)
4.3.13 205Ch - Service Required (DP/MP)
4.3.14 205Eh - Warning Present (DP/MP)
4.3.15 2060h - Error Present (DP/MP)
4.3.16 2062h - Final Error Present (DP/MP)
4.3.17 2064h - Rotating Direction (System)
4.3.18 206Dh - Base Load Pump
4.3.19 206Eh - Number of Active DP/MP Pumps
4.3.20 2070h - Pump Digital Outputs
4.3.21 2072h - Pump Digital Inputs
4.3.22 2076h - IF-Module
4.3.23 2077h - Actual Value Sensor Source
4.4  Section Measurement
4.4.1 2083h - Speed (DP/MP)
4.4.2 2087h - Estimated Flow (System)
4.4.3 2088h - Estimated Flow Range Min (System)
4.4.4 2089h - Estimated Flow Range Max (System)
4.4.5 208Bh - Estimated Pressure (System)
4.4.6 208Ch - Estimated Pressure Range Min (System)
4.4.7 208Dh - Estimated Pressure Range Max (System)
4.4.8 2090h - Input Power (System)
4.4.9 2091h - Electrical Current (System)
4.4.10 2092h - Voltage Level (DP/MP)
4.4.11 2093h - Input Power (DP/MP)
4.4.12 2094h - Electrical Current (DP/MP)
4.4.13 20A0h - Medium Temperature (System)
4.5  Section Messaging (Service and Errors)
4.5.1 20C1h - Current Warning/Error
4.5.2 20C2h - Current Warning/Error (DP/MP)
4.5.3 20E0h - Error History Code (Master)
4.5.4 20E1h - Error History Code (Slave 1)
4.6  Section Statistic
4.6.1 2101h - Operation Time Resettable (System)
4.6.2 2103h - Operation Time Resettable
4.6.3 2104h - Parallel Operation Time Resettable
4.6.4 2108h - Mains Time
4.6.5 2109h - Uptime (System)
4.6.6 2110h - Mains On Counter
4.6.7 2111h - Pump Kick Counter
4.6.8 2112h - Auto Night Mode Counter
4.6.9 2113h - Consumption (System)
4.6.10 2114h - Consumption
4.6.11 212Fh - Q-Histogramm
4.7  Section Constants
4.7.1 2182h - Pump Type
4.7.2 218Bh - Pump Type Name
4.7.3 218Ch - This Pump Function
4.7.4 218Dh - This Pump Location/Name
4.7.5 21A0h - Min Speed (System, CONST_SPEED)
4.7.6 21A1h - Max Speed (CONST_SPEED)
4.7.7 21A4h - Min Pressure dp-v (VAR_DIFFPRESS)
4.7.8 21A5h - Max Pressure dp-v (VAR_DIFFPRESS)
4.7.9 21A7h - Max Flow
4.7.10 21A8h - Min Medium Temperature
4.7.11 21A9h - Max Medium Temperature
4.7.12 21ABh - Max Input Power
4.7.13 21ACh - Min Pressure dp-c
4.7.14 21ADh - Max Pressure dp-c
4.8  Section Configuration
4.8.1 2201h - dp-c = f(T) Regulation Tmin
4.8.2 2202h - dp-c = f(T) Regulation Tmax
4.8.3 2203h - dp-c = f(T) Regulation Pmin
4.8.4 2204h - dp-c = f(T) Regulation Pmax
4.8.5 2207h - HV/AC System Error Detection
4.8.6 2208h - Error Auto Reset Time
4.8.7 2229h - Automatic Night Mode
4.8.8 2232h - SBM Relay Mode
4.8.9 2233h - SSM Relay Mode
4.8.10 2234h - External Setpoint Linearity
4.8.11 2235h - External Setpoint Signal Type
4.8.12 2250h - Pump Kick Event
4.8.13 2251h - Pump Kick Interval
4.8.14 225Bh - Menu Settings Lock
4.8.15 225Dh - Display Orientation
4.8.16 225Eh - Display Unit
4.9  Section Double/Multi Pump
4.9.1 2315h - DP-Modus
4.9.2 2320h - Pump Swap Event
4.9.3 2322h - Pump Swap Interval
4.9.4 2323h - Member Pump Enable
4.9.5 2332h - SBM Relay Collective
4.9.6 2333h - SSM Relay Collective
4.10  Section CAN Configuration
4.10.1 2400h - CANopen Address
4.10.2 2403h - Auto Operational Mode
5    Versioning and Support
5.1  CAN Revision History
5.2  CAN Revision Support
5.3  Parameter Support
5.3.1 Section CANopen
5.3.2 Section Control
5.3.3 Section Status
5.3.4 Section Measurement
5.3.5 Section Messaging (Service and Errors)
5.3.6 Section Statistic
5.3.7 Section Constants
5.3.8 Section Configuration
5.3.9 Section Double/Multi Pump
5.3.10 Section CAN Configuration

1    Introduction

1.1  About this Document

Motivation
In order to make configuration and operation easier, many building components support some way of remote controlling. This remote controlling does not only make it possible for the janitor to monitor devices and open gates or doors, letting the roller blinds down etc. But it also to makes automatic changes, as turning down the temperature at 6 p.m. or perhaps even when the last person has left the building.
In short: The communication between devices are becoming more and more common, and more and more different devices are connected to the main computer in order to allow what could be seen as an intelligent building.
This document describes the protocol that will enable a remote control of pumps and thus make it possible to incorporate them in the main building management system.
Value Notation
All values in this document are decimal unless prefixed with "0x" for a hexadecimal value. The exception is the Example Telegrams, they are always in hexadecimal format (see below).
Example Telegrams
In this Document there are some communication samples, they looking like:
701 1 05
Operational Heartbeat
181 8 00 00 05 00 00 10 03 80
TxPDO1
The first block of three numbers is the hexadecimal 11-Bit CAN-ID, thereafter is a single number ranging from 0 through 8, it tells the user how many data bytes are transmitted. Last are the data bytes, each byte always in block of two hexadecimal numbers. After the numbers comes a brief explanation of the Telegram.
Symbols
Important information about something specific is written like this. It can contain tips and/or the information can be important and should be respected.

1.2  Scope of the Document

What and to Whom?
This document describes the protocol and is targeted to developers that need to communicate with Wilo pumps.
First Chapter
A description of this document.
Second Chapter
Contains CAN Hardware Requirements and a simple way to interface with Wilo Pumps with a normal CAN device. No knowledge of CANopen is required at this point.
Third Chapter
Contains what CANopen features are supported, the Wilo specific portions of the protocol and how the Wilo device behaves in certain situations. In depth Error Handling, Status bits, PDO Regulation and other features are described in depth here.
Fourth Chapter
Contains all SDO Parameters that can be read or written.
Fifth Chapter
Contains a list of all supported Wilo Devices and what Parameters they support. Different Revisions are also listed here
Sixth Chapter
Contains detailed communication examples to a Wilo Device.
More information
More information about Networking with Wilo products can be found at www.wilo.com/automation. The CANopen Standards and other CANopen information can be found at www.canopen.org.

1.3  Terms

Bus
The communication over the CAN-Interface.
CAN
Controller Area Network
CANopen
A Specification from CiA, CAN in Automation.
Device On
The device is operating (a pump is actively pumping fluids).
Device Off
The device is not operating (a pump does not actively pump fluids), however it still has power and can communicate over a network.
Device Power Off
The pump has no longer any power and cannot communicate at all.
DP
Double Pump, two pumps in the same housing.
(DP/MP)
Denotes a parameter that contains values for each device in the system. See System and (System)
Effective
The value at which the Pump or System operates. See Selected
MP
Multipump, two to six pumps working parallel in their own housing.
NodeId
The Bus Address of a device.
Selected
The wanted value at which the Pump or System should operate. See Effective
System
A collection of several devices that answer on a single CAN-interface. See DP or MP
(System)
Denotes a Parameter that contains a value for the complete System. See System and (DP/MP)

2    CAN

2.1  CAN Overview

Bus Topology
The CAN devices should be connected in a line, where each device may be connected to at most 2 other devices. An exception to this rule is possible (it is called Stub), see Cable Stubs below.
The NodeId must be configured at each device (node), before this node can be added to the network. The NodeId can range from 1 to 127. However in order to use some Wilo specific features it is recommended to use the NodeId range 1 to 64.
Please make sure that each NodeId is unique within the same network. If two nodes has the same NodeId it might go unnoticed, but data will collide and data will be lost.
Data Flow
CAN is a Multi-Master Network, that means that all devices can initiate a telegram themselves. Basically all Devices broadcast their current status on the network and all devices that has usage of this info can use it. Some CANopen terms for this automatic sending are Heartbeat, PDO, EMCY and TIME.
It is also possible to request data from a specific Device, like the more conventional "Master-Slave"-communication. The CANopen term for this communication type is SDO.

2.2  Hardware Restrictions

Cable Length
The maximal length of the cable is 200m (including stubs).
Cable Stubs
It is allowed to split the cable line, the smaller branches are called stubs and may be up to 10 m. Please note that the total length of these stubs may not be more than 50 m. The total allowed cable length is including these stubs.
Baud Rate
The Wilo CANopen devices support 125 KBit/s.

2.3  Simple Communication

Overview
It is possible to communicate with Wilo CANopen devices without knowledge about CANopen, this can be extra interesting for simple PLC and BMS Systems.
Reading Device Data
The Wilo Devices are continuously sending information about itself on the bus. This Data can be read directly without any difficult implementation, a description of this can be found in the following sections.
Writing Device Data
In order to write values to the Wilo Device, two CAN Identifiers must be sent. The first one is the Generated Heartbeat (a constant message sent every second) and the other is the wanted settings: binding on/off, device on/off, setpoint, regulation mode and min/max modes. More information can be found in the following sections.
Mixing Simple and Complex Commands
The simplified information described here may not be used together with the more complex commands from other chapters without fully understanding the complete implication of this.

2.3.1 Bootup and Heartbeat

Device Bus Address (NodeId)
The address of a Wilo Device must be configured at the device itself, often through the use of a menu. The Bus Address is called NodeId.
When using this Simple Communication please take care to set a NodeId between 1 and 64 (it is possible to select a NodeId up to 127, but a Wilo device with such a high NodeId will not support the simple communication described here).
Bus Presence
A Wilo device sends a Heartbeat every second on the bus. This heartbeat can be used to see if a specific device is present or not.
Bootup Sequence
When the Wilo device is powered up it sends a Bootup telegram. This bootup is followed by 5 seconds of Pre-Operational telegrams (telling others that this device is ready). After this, the main Operational state is entered as can be seen in the following example:
701 1 00
Bootup
701 1 7F
Pre-Operational Heartbeat
701 1 7F
Pre-Operational Heartbeat
701 1 7F
Pre-Operational Heartbeat
701 1 7F
Pre-Operational Heartbeat
701 1 05
Operational Heartbeat
Simple Heartbeat Description
A Heartbeat has the CAN-ID ranging from 0x701 to 0x77F (0x700+NodeId). It must always have 1 Byte data, and this byte can be one of the following.
00: Bootup
7F: Pre-Operational
05: Operational
Bootup Detection
A Bootup telegram can be used to detect if a new device has been introduced to the network, or if a present device has lost its power temporary.
Device Presence Detection
If a Wilo Device Heartbeat is not seen for more than 2 seconds (double the Heartbeat time) this device can be considered lost (detached from the network or powered off).

2.3.2 Simple Read

Here are the messages explained that are sent from the Wilo Device.
Regulation Data
This data is sent "on change" but at least every second. It contains the current load, the current control mode and status (on/off, error and a lot more) of the device.
AAA B CC CC DD EE FF GG HH II
Regulation Data example message
AAA is the value 384 (0x180) plus the NodeId of the device.
B ist the number of bytes in this packet, it can be 0, 2, 3, 4, 5, 6, 7 or 8.
CCCC is the System Actual Capacity in 0.01 Percent steps (see Par 2040h - Effective Capacity (System)), sent with low byte first.
DD is the System Control Mode. 0=n-c, 4=p-c, 5=dp-c, 6=dp-v, 11=dp-c=f(T), 12=PID. (see Par 2041h - Effective Control Mode (System)).
EE is the system command, bit 0=Pump On, bit 1=Ext Off Active, bit 2=Ext Max Active, bit 3=Ext Min Active, bit 4=Ext On Active. (see Par 2042h - Effective Command (System)).
Additional Data
This data is sent "on change" but at least every 5 seconds. It contains the current power rating, pressure and medium temperature.
AAA B CC CC CC CC DD DD EE EE
Additional Data example message
AAA is the value 640 (0x280) plus the NodeId of the device.
B ist the number of bytes in this packet, it can be 0, 4, 6 or 8.
CCCCCCCC is the Power Rating in mW (see Par 2090h - Input Power (System)), sent with low byte first.
DDDD is the Current Pressure in 0,1 kPa (see Par 208Ah - Pressure (System) or Par 208Bh - Estimated Pressure (System)), sent with low byte first..
EEEE is the temperature in 0,1 K (see Par 20A0h - Medium Temperature (System)), sent with low byte first..
Multiplexed Data
This data is sent "on change" and each Measured Value is sent at least every minute. It can contain Voltage, Flow, Consumption, Operation Time and similar .
AAA B CC DD DD EE FF FF FF FF
Multiplexed Data example message
AAA is the value 896 (0x380) plus the NodeId of the device.
B ist the number of bytes in this packet, it is always 8
CC is the NodeId of the Device transmitting this data (the same as AAA
DDDD is the Index of the data following in FFFFFFFF, it is sent with the low byte first.
EE is the subindex of the data following in FFFFFFFF
FFFFFFFF is the data of the specified index and subindex, it is sent with the low byte first..
Error Signaling
This data is only sent if an Error is generated or when it is acknowledged. It also contains some status info about the error.
AAA B CC DD EE FF GG HH II II
Error Signaling example message
AAA is the value 128 (0x80) plus the NodeId of the device.
B ist the number of bytes in this packet, it is always 8.
CC is the Wilo Error Type, 0x00=Last Message Acknowledged (No Service, Warning, Error or Final Error), 0x53=Service Message, 0x57=Warning Message, 0x45=Error Message, 0x46=Final Error Message.
DD is reserved
EE is reserved
FF is the wilo Error Code (see Product Documentation).
GG is the location, 0=Master, 1=Slave.
HH is reserved
IIII is reserved.

2.3.3 Simple Write Prerequisities

Generate Heartbeat
In order to use the Simple Communication described here, the device that is to communicate with the Wilo device must generate a heartbeat with a cycle of 1 seconds at the NodeId from the Wilo Device plus 64 (0x40). This Heartbeat must also contain the code Operational (05).
Example
If a Wilo Device is set to NodeId 9. A hearbeat with a 1 second cycle must be generated at NodeId 73 (0x49).
709 1 00
Wilo Device
709 1 7F
Wilo Device
709 1 7F
Wilo Device
749 1 05
Generated Operational Heartbeat
709 1 7F
Wilo Device
749 1 05
Generated Operational Heartbeat
709 1 7F
Wilo Device
749 1 05
Generated Operational Heartbeat
709 1 05
Wilo Device
749 1 05
Generated Operational Heartbeat
709 1 05
Wilo Device
749 1 05
Generated Operational Heartbeat
709 1 05
Wilo Device
749 1 05
Generated Operational Heartbeat
Control Detection
As soon as the setpoints arrive at the pump the possibility to change the setpoint locally is disabled. The Generated Heartbeats are also monitored by the Wilo Device, and if a Generated Heartbeat is not seen within 2 seconds, an error (E54 Binding Lost) is generated in the pump. With this Error, the local setpoint menu is enabled again.
Make sure that the generated Heartbeat is sent every second. If the pump does not receive a Heartbeat after 2 seconds, it will disable the Simple Write function and generate E54. If the heartbeat then starts again, E54 will disappear and the pump will activate the Simple Write function again.

2.3.4 Simple Write

This data can be sent when a change should be issues, but it is a better practice to send the data continuously, depending on how "responsive" the system should be. When regulating actively it can be up to a 50ms cycle (at these speeds the bus usage must be monitored). If not imporatant at all the cycle can be about a minute or an hour. Usually it is about 5 seconds. It contains the wanted load, the wanted control mode and wanted on/off status (on/off, max min and some more).
AAA B CC CC DD EE
Regulation Data example message
AAA is the value 256 (0x200) plus the NodeId of the device.
B ist the number of bytes in this packet, it must be equal to 4.
CCCC is the Wanted System Capacity in 0.01 Percent steps (see Par 2008h - Bus Setpoint (System)), sent with low byte first.
DD is the Wanted Control Mode. 0=n-c, 4=p-c, 5=dp-c, 6=dp-v, 11=dp-c=f(T), 12=PID. (see Par 2009h - Bus Control Mode (System)).
EE is the system command, bit 0=Pump On, bit 1=Ext Off Active, bit 2=Ext Max Active, bit 3=Ext Min Active, bit 4=Ext On Active, bit 5 activates the CCCC portion and bit 6 activates the DD EE portion. (alse see Par 204Ah - Selected Command (System)).
Make sure that bit 5 and 6 of portion EE is set as wanted. If set as '1' it simultaneously blocks this function in the pump menu. If set to '0' the specified portion in the Simple Write is ignored.
Make sure that the Simple Write Prerequisities are met before using simple writes. If they are not met, the Simple write will not work.

2.3.5 Simple One Time Configuration

This configuration should only be sent once for initialization. It is not good practice to send this automatically and it must be taken care that only one device in each network issues these commands. These commands do not depend on the Simple Write Prerequisities above, and may be executed without the generated Hertbeat.
Write Byte
AAA B 0x2F CC CC DD EE 00 00 00
Write byte example message
FFF B 0x60 CC CC DD 00 00 00 00
Write byte response message
AAA is the value 1536 (0x600) plus the NodeId of the device.
B ist the number of bytes in this packet, it must be equal to 8.
CCCC is the Parameter index that is to be written
DD is the Parameter subindex that is to be written
EE is the value that should be written.
FFFF is the value 1408 (0x580) plus the NodeId of the device.
Write Word
AAA B 0x2B CC CC DD EE EE 00 00
Write word example message
FFF B 0x60 CC CC DD 00 00 00 00
Write word response message
AAA is the value 1536 (0x600) plus the NodeId of the device.
B ist the number of bytes in this packet, it must be equal to 8.
CCCC is the Parameter index that is to be written
DD is the Parameter subindex that is to be written
EEEE is the value that should be written.
FFFF is the value 1408 (0x580) plus the NodeId of the device.
Write Double Word
AAA B 0x23 CC CC DD EE EE EE EE
Write double word example message
FFF B 0x60 CC CC DD 00 00 00 00
Write double word response message
AAA is the value 1536 (0x600) plus the NodeId of the device.
B ist the number of bytes in this packet, it must be equal to 8.
CCCC is the Parameter index that is to be written
DD is the Parameter subindex that is to be written
EEEEEEEE is the value that should be written.
FFFF is the value 1408 (0x580) plus the NodeId of the device.
Read Byte
AAA B 0x40 CC CC DD 00 00 00 00
Read byte example message
FFF B 0x4F CC CC DD EE 00 00 00
Read byte response message
AAA is the value 1536 (0x600) plus the NodeId of the device.
B ist the number of bytes in this packet, it must be equal to 8.
CCCC is the Parameter index that is to be read
DD is the Parameter subindex that is to be read
EE contains the read value.
FFFF is the value 1408 (0x580) plus the NodeId of the device.
Read Word
AAA B 0x40 CC CC DD 00 00 00 00
Read word example message
FFF B 0x4B CC CC DD EE EE 00 00
Read word response message
AAA is the value 1536 (0x600) plus the NodeId of the device.
B ist the number of bytes in this packet, it must be equal to 8.
CCCC is the Parameter index that is to be read
DD is the Parameter subindex that is to be read
EEEE contains the read value.
FFFF is the value 1408 (0x580) plus the NodeId of the device.
Read Double Word
AAA B 0x40 CC CC DD 00 00 00 00
Read double word example message
FFF B 0x43 CC CC DD EE EE EE EE
Read double word response message
AAA is the value 1536 (0x600) plus the NodeId of the device.
B ist the number of bytes in this packet, it must be equal to 8.
CCCC is the Parameter index that is to be read
DD is the Parameter subindex that is to be read
EEEEEEEE contains the read value.
FFFF is the value 1408 (0x580) plus the NodeId of the device.
If One of the above messages cannot be executed by the pump, it will return an Error Message.
AAA B 0x80 CC CC DD EE EE EE EE
Simple configuration Error Response
AAA is the value 1408 (0x580) plus the NodeId of the device.
B ist the number of bytes in this packet, it is always equal to 8.
CCCC is the Parameter index that was requested
DD is the Parameter subindex that was requested
EEEEEEEE contains the error code.

3    CANopen

CANopen is a fieldbus protocol and has several mechanisms that can be supported, this chapter describes what is supported.

3.1  Supported Communication Objects

Heartbeat
All devices support the Heartbeat feature of CANopen. The heartbeat signals a presence on the bus, all units must send its heartbeat since it is used for "binding" units together. Devices supporting only Node-Guarding should not be used in the same network as the Wilo Devices.
PDO
tx and rx PDOs are supported, some PDOs can be configured (Transmission types 0-240 and 254, Inhibit Time and Event Timer are supported).
MPDO
Values that are not needed very often are sent on change with a SAM MPDO.
SDO
Expedited and Segmented Upload/Download are supported.
SYNC
Is supported (see PDO)
TIME
Most Wilo devices are TIME consumers. It enables a timestamp in the error history.
EMCY
Is supported.
NMT
Is supported.
LSS
Is not supported and should not be used together with Wilo Devices.

3.2  EMCY Codes (CAN 1.01)

This data is only sent if an Error is generated or when it is acknowledged. It also contains some status info about the error.
AAA B CC DD EE FF GG HH II II
Error Signaling example message
AAA is the value 128 (0x80) plus the NodeId of the device.
B ist the number of bytes in this packet, it is always 8.
CC is the Wilo Error Type, 0x00=Last Message Acknowledged (No Service, Warning, Error or Final Error), 0x53=Service Message, 0x57=Warning Message, 0x45=Error Message, 0x46=Final Error Message.
DD is reserved
EE is reserved
FF is the wilo Error Code (see Product Documentation).
GG is the location, 0=Master, 1=Slave.
HH is reserved
IIII is reserved.

3.3  Error Status Bits

There are four different Error Status Bits and several can be set at the same time. For example: A Final Error would set the Error Bit as well.
Service/Maintenance
This bit is set when service is required locally at the location of the pump. For example after a final E21 (Motor Overload) or a Service interval is due (Mechanical Seal is due for replacement). Errors marked with this bit must be acknowledged locally (Red Button or over Infrared control).
Warning
This bit is set if an Error is present and the device can still run, For example, E40, E50, E52. Errors marked with this bit can be acknowledged locally. They are also automatically acknowledged when the Error is no longer present.
Error
This bit is set if an Error is present and the motor must be turned off. For example E21, E10. Errors marked with this bit will be resetted automatically if the error is no longer present.
Final Error
This bit is set if a Final Error has occured. For example E21 with the 6th Error or E10. Errors marked with this bit usually also has the service bit set and can be acknowledged locally.

3.4  CAN Specific Errors

E53 NodeId in Use
If a Wilo device sees a Heartbeat with its own NodeId on the Network, it disconnects from the network (sets its own address to OFF) and signals E53. This Warning must be acknowledged and a valid NodeId must be set before it is possible to communicate with this device.
E54 Binding Lost
If a CAN/CANopen Device is binded with the Wilo Device and its Hearbeat ceases to exist, the Wilo device disables the binding and signals E54.

3.5  Parameter Description Sample

The title of each parameter contains the parameter number (in Hex). This is the CANopen "Index". If a subindex is present it is written in text behind the index.
Description
This description describes the Parameter, what it can do or what it contains.
If there is something important that must be done, it is usually written like this.
Dependency
Dependencies to other Parameters are described here.
can change meaning: usually means that the respect of the parameter changes. For example 100% in CONTROL_SPEED is max rpm, and 100% in CONTROL_PRESSURE is max kPa
Parameter is disabled: a write returns an error message
CAN write access to This Parameter is disabled: If the mentioned protocol writes the Parmeter, an error is returned.
Bitset Description
If the Parameter formatting is Bitset, the following list will be present. It contains the bits and their relevance.
Bit Bit equals Zero Bit equals One
0 pump off  pump on
1 feature deactivated  feature activated
Parameter Specification
Specification
VariableType The size and type of the variable is described here, some eamples are UNSIGNED8, SIGNED16 or VISIBLE_STRING. A description of the typed can be found in the CiA Draft Standard 301, Version 4.02, page 25
Volatile Yes, means that the parameter is lost on Power off, and no means that it is saved on changed or per Parameter 1010h.
Formatting the Unit of the parameter, for example Bitset, 0,1V, Seconds, etc
Valid Values the range of the valid values, if values outside of this range is written, and error is returned.
Error Value if the Parameter contains exactly this value, the value is not calculable or valid at the moment. It should be displayed as "Invalid" or "N/A" to the user.
Access read or write access
PDO Mappable if it is possible to map this parameter to a PDO.
Device Support and Default Value
SupportDefault
Stratos if "no support" is written here, the specified index or subindex is not supported by the pump family

4 Complete - Parameter Documentation

4.1 Section CANopen

4.1.1 1000h - Device Type

Description
Contains information about the device type. The lower 16 bit contain the Device Profile Number and the upper 16 bit contain the Additional Information. The Wilo CAN bus contains the value 0000 0000h (deviceprofile 0000h and no additional information).
For more information see CiA Draft Standard 301, Version 4.02, page 86
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no
Formatting Spec
Valid Values 0 to 0xFFFFFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel 0

4.1.2 1001h - Error Register

Description
The error register is a field of 8 bits, each for a certain error type. If an error occurs the bit has to be set. Wilo Pumps only support Generic Error and Manufacturer Error.
For more information see CiA Draft Standard 301, Version 4.02, page 87
Bitset Description
Bit Bit equals Zero Bit equals One
default  generic error 
default  current 
default  voltage 
default  temperature 
default  communication error (overrun, error state) 
default  device profile specific 
default  reserved 
default  manufacturer error 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.1.3 1003h - Pre-defined Error Field

Description
This object holds errors that have occurred on the device and have been signalled via Emergency Object. It is an error history. Writing to sub index 0 deletes the entire error history. The values in this parameter are not stored in EEPROM, for a more detailed error history list see Par 20E0h - Error History Code (Master), Par 20E6h - Error History Date (Master) and Par 20ECh - Error History Operation Hours (Master).
For more information see CiA Draft Standard 301, Version 4.02, page 88
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Errors 0
1 Standard Error Field no default
2 Standard Error Field no default
3 Standard Error Field no default
4 Standard Error Field no default
5 Standard Error Field no default
6 Standard Error Field no default
7 Standard Error Field no default
8 Standard Error Field no default
IL-E support the following Subindexes
0 Number of Errors 0
1 Standard Error Field no default
2 Standard Error Field no default
3 Standard Error Field no default
4 Standard Error Field no default
5 Standard Error Field no default
6 Standard Error Field no default
7 Standard Error Field no default
8 Standard Error Field no default
MXIE support the following Subindexes
0 Number of Errors 0
1 Standard Error Field no default
2 Standard Error Field no default
3 Standard Error Field no default
4 Standard Error Field no default
5 Standard Error Field no default
6 Standard Error Field no default
7 Standard Error Field no default
8 Standard Error Field no default
ServicePanel support the following Subindexes
0 Number of Errors 0
1 Standard Error Field no default
2 Standard Error Field no default
3 Standard Error Field no default
4 Standard Error Field no default
5 Standard Error Field no default
6 Standard Error Field no default
7 Standard Error Field no default
8 Standard Error Field no default
4.1.3.1 1003h Subindex 0 - Number of Errors
Description
This Subindex contains the number of following subindexes.
This Subindex is writeable, but only the value 0 is accepted, any other value generates an abort message (error code: 0609 0030h).
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 0xFE
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel 0
4.1.3.2 1003h Subindex 1 - Standard Error Field
Description
This Subindex contains a record of the last signalled error.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting Spec
Valid Values 0 to 0xFFFFFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.1.3.3 1003h Subindex 8 - Standard Error Field
Description
This Subindex contains a record of the 8th last signalled error.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting Spec
Valid Values 0 to 0xFFFFFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.1.4 1005h - COB-ID SYNC

Description
COB-ID of the Synchronization object. The device listens to the SYNC COB-ID written in this message.
For more information see CiA Draft Standard 301, Version 4.02, page 89.
The bits 29 and 30 are not supported and must be 0.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 1 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x80
IL-E 0x80
MXIE 0x80
ServicePanel 0x80

4.1.5 1008h - Manufacturer Device Name

Description
Contains the device name (Example: 'Stratos 30/1-12').
For more information see CiA Draft Standard 301, Version 4.02, page 91
Parameter Specification
Specification
VariableType VISIBLE_STRING
Volatile no
Formatting Text
Valid Values 0 to 32
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.1.6 100Ah - Manufacturer Software Version

Description
Pump software number (Example: '5.02').
For more information see CiA Draft Standard 301, Version 4.02, page 91
Parameter Specification
Specification
VariableType VISIBLE_STRING
Volatile no
Formatting Text
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.1.7 1010h - Store Parameter Field

Description
This entry supports saving of parameters in non volatile memory. With a read access the device provides information about its saving capabilities. Several parameter groups are distinguished. To save, the signature 'save' (0x65766173) must be written to the wanted Subindex.
Wilo devices support only save on demand for the communication parameters (0x1000 to 0x1FFF), the application parameters (0x2000 to 0x27FF) are saved directly when they are changed.
For more information see CiA Draft Standard 301, Version 4.02, page 92.
Device Support and Default Values
4.1.7.1 1010h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 0x7F
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 3
IL-E 3
MXIE 3
ServicePanel 3
4.1.7.2 1010h Subindex 1 - All Parameters
Description
This Subindex is not supported.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting Spec
Valid Values to
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel 0
4.1.7.3 1010h Subindex 2 - Communication Parameters (1000h-1FFFh)
Description
When this subindex is written, the current Communication Parameters (0x1000-0x1FFF) are stored in EEPROM.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting Spec
Valid Values to
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1
IL-E 1
MXIE 1
ServicePanel 1
4.1.7.4 1010h Subindex 3 - Application Parameters (2000h-27FFh)
Description
This Subindex is not supported.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting Spec
Valid Values to
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 2
IL-E 2
MXIE 2
ServicePanel 2

4.1.8 1011h - Restore Default Parameters

Description
Several parameter groups are distinguished. To restore from EEPROM, the signature 'load' (0x64616f6c) must be written to the specified subindex.
For more information see CiA Draft Standard 301, Version 4.02, page 94.
Device Support and Default Values
4.1.8.1 1011h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 0 to 0x7F
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 3
IL-E 3
MXIE 3
ServicePanel 3
4.1.8.2 1011h Subindex 1 - All Parameters
Description
This restores all Parameters to default (Factory Setting). Statistic Parameters (counters, operation time) and Error History are not reset.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting Spec
Valid Values to
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1
IL-E 1
MXIE 1
ServicePanel 1
4.1.8.3 1011h Subindex 2 - Communication Parameters (1000h-1FFFh)
Description
This restores all Communication Parameters (1000-1FFF) to default (Factory Setting)
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting Spec
Valid Values to
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1
IL-E 1
MXIE 1
ServicePanel 1
4.1.8.4 1011h Subindex 3 - Application Parameters (2000h-27FFh)
Description
This restores all Application Specific Parameters (2000-27FF) to default (Factory Setting). Statistic Parameters (counters, operation time) and Error History are not reset.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting Spec
Valid Values to
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1
IL-E 1
MXIE 1
ServicePanel 1

4.1.9 1012h - COB-ID Time Stamp

Description
COB-ID of the Time Stamp Object (TIME). If bit 31 is set the device consumes the Time Stamp message and if bit 30 is set the device produces the Time Stamp message. The meaning of the other bits is equal to the other communication objects.
For more information see CiA Draft Standard 301, Version 4.02, page 97.
The bits 29 and 30 are not supported and must be 0.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 1 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x80000100
IL-E 0x80000100
MXIE 0x80000100
ServicePanel 0x80000100

4.1.10 1014h - COB-ID EMCY

Description
Error Broadcast function. COB-ID used for emergency message (Emergency Server).
For more information see CiA Draft Standard 301, Version 4.02, page 98.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 1 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos $NODEID+0x00000080
IL-E $NODEID+0x00000080
MXIE $NODEID+0x00000080
ServicePanel $NODEID+0x00000080

4.1.11 1016h - Consumer Heartbeat Time

Description
The consumer heartbeat time defines the expected heartbeat cycle time and thus has to be higher than the corresponding producer heartbeat time configured on the device producing this heartbeat. Monitoring starts after the reception of the first heartbeat. If the consumer heartbeat time is 0 the corresponding entry is not used. The time has to be a multiple of 1ms.
For more information see CiA Draft Standard 301, Version 4.02, page 100.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 1
1 Consumer Heartbeat Time (I/O Module) 0x004107D0
IL-E support the following Subindexes
0 Number of Entries 1
1 Consumer Heartbeat Time (I/O Module) 0x004107D0
MXIE support the following Subindexes
0 Number of Entries 1
1 Consumer Heartbeat Time (I/O Module) 0x004107D0
ServicePanel does not support this Array
4.1.11.1 1016h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 1 to 2
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1
IL-E 1
MXIE 1
ServicePanel no support
4.1.11.2 1016h Subindex 1 - Consumer Heartbeat Time (I/O Module)
Description
This contains the NodeId and the Heartbeat Time of the I/O Module (or Gateway). If the heartbeat time is equal to 0, no heartbeat is checked, and the bus-control mode is completely operational. If the heartbeat time is unequal to 0 then the heartbeat must be present in order to activate the Bus-Control Mode (see Par 200Ah Bit 5 - Activate Bus Setpoint for more info). If the heartbeat is lost and the Heartbeat Time is unequal to 0, then the pump sets the extern Off/Max/Min/On bits to 0, (exception, If Ext-Off was active the pump is turned off. If Ext-Max, Ext-Min or Ext-On was activated the pump returns to its previous state). The bits Par 200Ah Bit 5 - Activate Bus Setpoint and Par 200Ah Bit 6 - Activate Bus Control Mode are reset to 0. An Error is also triggered.
The default value of NodeId (bit 16 to 23) is $NODEID+64. NodeId must not be equal to the NodeId of this device or any other subindex of Par 1016h - Consumer Heartbeat Time, and it must be in the range of 1 to 127.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Bitset Description
Bit Bit equals Zero Bit equals One
0-15  Heartbeat Time (ms)   
16-23  NodeId   
24-31  Reserved (Always 0)   
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0 to 0x7FFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x004107D0
IL-E 0x004107D0
MXIE 0x004107D0
ServicePanel no support

4.1.12 1017h - Producer Heartbeat Time

Description
The producer heartbeat time defines the cycle time of the heartbeat. If the time is 0 it is not used. The time has to be a multiple of 1 msec.
For more information see CiA Draft Standard 301, Version 4.02, page 101.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 1 ms
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1000
IL-E 1000
MXIE 1000
ServicePanel 1000

4.1.13 1018h - Identity Object

Description
This object contains general information about the device.
For more information see CiA Draft Standard 301, Version 4.02, page 101.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 4
1 Vendor Id 0x239
2 Product Code no default
3 Revision number no default
4 Serial number no default
IL-E support the following Subindexes
0 Number of Entries 4
1 Vendor Id 0x239
2 Product Code no default
3 Revision number no default
4 Serial number no default
MXIE support the following Subindexes
0 Number of Entries 4
1 Vendor Id 0x239
2 Product Code no default
3 Revision number no default
4 Serial number no default
ServicePanel support the following Subindexes
0 Number of Entries 4
1 Vendor Id 0x239
2 Product Code no default
3 Revision number no default
4 Serial number no default
4.1.13.1 1018h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 1 to 4
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 4
IL-E 4
MXIE 4
ServicePanel 4
4.1.13.2 1018h Subindex 1 - Vendor Id
Description
contains a unique value allocated each manufacturer. Wilo devices will contin the number 0x239 ('WILO').
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no
Formatting Number
Valid Values 0 to 0xFFFFFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x239
IL-E 0x239
MXIE 0x239
ServicePanel 0x239
4.1.13.3 1018h Subindex 2 - Product Code
Description
identifies the manufacturer specific product code. Wilo products stores their Article Number In this subindex.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFFFFFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.1.13.4 1018h Subindex 3 - Revision number
Description
contains the revision number.
Bit 31-16 is the major revision number and Bit 15-0 the minor revision number. (Contains a CAN open revision number, see CANopen v4.02 p.101)
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no
Formatting Number
Valid Values 0 to 0xFFFFFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.1.13.5 1018h Subindex 4 - Serial number
Description
identifies a manufacturer specific serial number. Wilo devices stores their Serial Number here. The format is (decimal) a number followed by production year, week ('NNNNNYYWW').The Decimal number 90512 would mean number '9', produced Week 12, 2005.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFFFFFFFF
Error Value 0
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.1.14 1200h - Server SDO Parameter 1

Description
The object contains the parameters for the SDOs for which the device is the server.
For more information see CiA Draft Standard 301, Version 4.02, page 103.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 2
1 COB-ID Client -> Server $NODEID+0x00000600
2 COB-ID Server -> Client $NODEID+0x00000580
IL-E support the following Subindexes
0 Number of Entries 2
1 COB-ID Client -> Server $NODEID+0x00000600
2 COB-ID Server -> Client $NODEID+0x00000580
MXIE support the following Subindexes
0 Number of Entries 2
1 COB-ID Client -> Server $NODEID+0x00000600
2 COB-ID Server -> Client $NODEID+0x00000580
ServicePanel support the following Subindexes
0 Number of Entries 2
1 COB-ID Client -> Server $NODEID+0x00000600
2 COB-ID Server -> Client $NODEID+0x00000580
4.1.14.1 1200h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 2 to 2
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 2
IL-E 2
MXIE 2
ServicePanel 2
4.1.14.2 1200h Subindex 1 - COB-ID Client -> Server
Description
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no
Formatting Spec
Valid Values 0x00000600 to 0xBFFFFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos $NODEID+0x00000600
IL-E $NODEID+0x00000600
MXIE $NODEID+0x00000600
ServicePanel $NODEID+0x00000600
4.1.14.3 1200h Subindex 2 - COB-ID Server -> Client
Description
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no
Formatting Spec
Valid Values 0x00000580 to 0xBFFFFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos $NODEID+0x00000580
IL-E $NODEID+0x00000580
MXIE $NODEID+0x00000580
ServicePanel $NODEID+0x00000580

4.1.15 1400h - Receive PDO Communication Parameter 1

Description
A Wilo Device will have this Receive PDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).
If a cyclic control of the pump is wanted, this is the preferred PDO. It is recommended to use the default configuration.
For more information see CiA Draft Standard 301, Version 4.02, page 106.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 2
1 COB-ID $NODEID+0x40000200
2 Transmission Type 0xFE
IL-E support the following Subindexes
0 Number of Entries 2
1 COB-ID $NODEID+0x40000200
2 Transmission Type 0xFE
MXIE support the following Subindexes
0 Number of Entries 2
1 COB-ID $NODEID+0x40000200
2 Transmission Type 0xFE
ServicePanel support the following Subindexes
0 Number of Entries 2
1 COB-ID $NODEID+0xC0000200
2 Transmission Type 0xFE
4.1.15.1 1400h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 2 to 5
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 2
IL-E 2
MXIE 2
ServicePanel 2
4.1.15.2 1400h Subindex 1 - COB-ID
The functions behind the bits 29 and 30 are not supported so bit 29 must be 0 and the bit 30 must be 1.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 1 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos $NODEID+0x40000200
IL-E $NODEID+0x40000200
MXIE $NODEID+0x40000200
ServicePanel $NODEID+0xC0000200
4.1.15.3 1400h Subindex 2 - Transmission Type
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0xFE
IL-E 0xFE
MXIE 0xFE
ServicePanel 0xFE

4.1.16 1600h - Receive PDO Mapping Parameter 1

Description
A Wilo Device will have this Receive PDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).
If a cyclic control of the pump is wanted, this is the preferred PDO. It is recommended to use the default configuration.
For more information see CiA Draft Standard 301, Version 4.02, page 109.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 3
1 Mapping Entry 1 0x20080010
2 Mapping Entry 2 0x20090008
3 Mapping Entry 3 0x200A0008
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
IL-E support the following Subindexes
0 Number of Entries 3
1 Mapping Entry 1 0x20080010
2 Mapping Entry 2 0x20090008
3 Mapping Entry 3 0x200A0008
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
MXIE support the following Subindexes
0 Number of Entries 3
1 Mapping Entry 1 0x20080010
2 Mapping Entry 2 0x20090008
3 Mapping Entry 3 0x200A0008
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
ServicePanel support the following Subindexes
0 Number of Entries 0
1 Mapping Entry 1 0x00000000
2 Mapping Entry 2 0x00000000
3 Mapping Entry 3 0x00000000
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
4.1.16.1 1600h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Number
Valid Values 0x00 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 3
IL-E 3
MXIE 3
ServicePanel 0
4.1.16.2 1600h Subindex 1 - Mapping Entry 1
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00000000 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x20080010
IL-E 0x20080010
MXIE 0x20080010
ServicePanel 0x00000000
4.1.16.3 1600h Subindex 8 - Mapping Entry 8
Description
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00000000 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x00000000
IL-E 0x00000000
MXIE 0x00000000
ServicePanel 0x00000000

4.1.17 1800h - Transmit PDO Communication Parameter 1

Description
A Wilo Device will have this Transmit PDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).
If a cyclic status of the pump is wanted, this is the preferred PDO. It is recommended to use the default configuration.
For more information see CiA Draft Standard 301, Version 4.02, page 111.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000180
2 Transmission Type 0xFE
3 Inhibit Time 500
4 Compatibility Entry no default
5 Event Timer 1000
IL-E support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000180
2 Transmission Type 0xFE
3 Inhibit Time 500
4 Compatibility Entry no default
5 Event Timer 1000
MXIE support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000180
2 Transmission Type 0xFE
3 Inhibit Time 500
4 Compatibility Entry no default
5 Event Timer 1000
ServicePanel support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0xC0000180
2 Transmission Type 0xFE
3 Inhibit Time 500
4 Compatibility Entry no default
5 Event Timer 1000
4.1.17.1 1800h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 2 to 5
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 5
IL-E 5
MXIE 5
ServicePanel 5
4.1.17.2 1800h Subindex 1 - COB-ID
The functions behind the bits 29 and 30 are not supported so bit 29 must be 0 and the bit 30 must be 1.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 1 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos $NODEID+0x40000180
IL-E $NODEID+0x40000180
MXIE $NODEID+0x40000180
ServicePanel $NODEID+0xC0000180
4.1.17.3 1800h Subindex 2 - Transmission Type
Description
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0xFE
IL-E 0xFE
MXIE 0xFE
ServicePanel 0xFE
4.1.17.4 1800h Subindex 3 - Inhibit Time
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 100 µs
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 500
IL-E 500
MXIE 500
ServicePanel 500
4.1.17.5 1800h Subindex 4 - Compatibility Entry
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Spec
Valid Values 0 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.1.17.6 1800h Subindex 5 - Event Timer
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 1 ms
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1000
IL-E 1000
MXIE 1000
ServicePanel 1000

4.1.18 1801h - Transmit PDO Communication Parameter 2

Description
A Wilo Device will have this Transmit PDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).
If cyclic measure values of the pump is wanted, this is the preferred PDO. It is recommended to use the default configuration.
For more information see CiA Draft Standard 301, Version 4.02, page 111.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000280
2 Transmission Type 0xFE
3 Inhibit Time 2000
4 Compatibility Entry no default
5 Event Timer 10000
IL-E support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000280
2 Transmission Type 0xFE
3 Inhibit Time 2000
4 Compatibility Entry no default
5 Event Timer 10000
MXIE support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000280
2 Transmission Type 0xFE
3 Inhibit Time 2000
4 Compatibility Entry no default
5 Event Timer 10000
ServicePanel support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0xC0000280
2 Transmission Type 0xFE
3 Inhibit Time 2000
4 Compatibility Entry no default
5 Event Timer 10000
4.1.18.1 1801h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 2 to 5
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 5
IL-E 5
MXIE 5
ServicePanel 5
4.1.18.2 1801h Subindex 1 - COB-ID
The functions behind the bits 29 and 30 are not supported so bit 29 must be 0 and the bit 30 must be 1.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 1 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos $NODEID+0x40000280
IL-E $NODEID+0x40000280
MXIE $NODEID+0x40000280
ServicePanel $NODEID+0xC0000280
4.1.18.3 1801h Subindex 2 - Transmission Type
Description
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0xFE
IL-E 0xFE
MXIE 0xFE
ServicePanel 0xFE
4.1.18.4 1801h Subindex 3 - Inhibit Time
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 100 µs
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 2000
IL-E 2000
MXIE 2000
ServicePanel 2000
4.1.18.5 1801h Subindex 4 - Compatibility Entry
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Spec
Valid Values 0 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.1.18.6 1801h Subindex 5 - Event Timer
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 1 ms
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 10000
IL-E 10000
MXIE 10000
ServicePanel 10000

4.1.19 1802h - Transmit MPDO Communication Parameter 3

Description
A Wilo Device will have this Transmit MPDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).
This PDO cannot be configured as a normal PDO, It is only possible to use this PDO as an MPDO. If cyclic measure values of the pump is wanted, this is the preferred PDO. Any Value can be added or removed from the Scanner list in Par 1FA0h - Object Scanner List..
For more information see CiA Draft Standard 301, Version 4.02, page 111.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000380
2 Transmission Type 0xFE
3 Inhibit Time 1000
4 Compatibility Entry no default
5 Event Timer 60000
IL-E support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000380
2 Transmission Type 0xFE
3 Inhibit Time 1000
4 Compatibility Entry no default
5 Event Timer 60000
MXIE support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000380
2 Transmission Type 0xFE
3 Inhibit Time 1000
4 Compatibility Entry no default
5 Event Timer 60000
ServicePanel support the following Subindexes
0 Number of Entries 5
1 COB-ID $NODEID+0x40000380
2 Transmission Type 0xFE
3 Inhibit Time 1000
4 Compatibility Entry no default
5 Event Timer 60000
4.1.19.1 1802h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 2 to 5
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 5
IL-E 5
MXIE 5
ServicePanel 5
4.1.19.2 1802h Subindex 1 - COB-ID
The functions behind the bits 29 and 30 are not supported so bit 29 must be 0 and the bit 30 must be 1.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 1 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos $NODEID+0x40000380
IL-E $NODEID+0x40000380
MXIE $NODEID+0x40000380
ServicePanel $NODEID+0x40000380
4.1.19.3 1802h Subindex 2 - Transmission Type
Description
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Spec
Valid Values 0x00 to 0xFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0xFE
IL-E 0xFE
MXIE 0xFE
ServicePanel 0xFE
4.1.19.4 1802h Subindex 3 - Inhibit Time
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 100 µs
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1000
IL-E 1000
MXIE 1000
ServicePanel 1000
4.1.19.5 1802h Subindex 4 - Compatibility Entry
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Spec
Valid Values 0 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.1.19.6 1802h Subindex 5 - Event Timer
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 1 ms
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 60000
IL-E 60000
MXIE 60000
ServicePanel 60000

4.1.20 1A00h - Transmit PDO Mapping Parameter 1

Description
A Wilo Device will have this Transmit PDO preconfigured, It is recommended to use this pre configured configuration.
For more information see CiA Draft Standard 301, Version 4.02, page 112.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 7
1 Mapping Entry 1 0x20400010
2 Mapping Entry 2 0x20410008
3 Mapping Entry 3 0x20420008
4 Mapping Entry 4 0x20500008
5 Mapping Entry 5 0x20520008
6 Mapping Entry 6 0x20540008
7 Mapping Entry 7 0x20560008
8 Mapping Entry 8 0x00000000
IL-E support the following Subindexes
0 Number of Entries 7
1 Mapping Entry 1 0x20400010
2 Mapping Entry 2 0x20410008
3 Mapping Entry 3 0x20420008
4 Mapping Entry 4 0x20500008
5 Mapping Entry 5 0x20520008
6 Mapping Entry 6 0x20540008
7 Mapping Entry 7 0x20560008
8 Mapping Entry 8 0x00000000
MXIE support the following Subindexes
0 Number of Entries 7
1 Mapping Entry 1 0x20400010
2 Mapping Entry 2 0x20410008
3 Mapping Entry 3 0x20420008
4 Mapping Entry 4 0x20500008
5 Mapping Entry 5 0x20520008
6 Mapping Entry 6 0x20540008
7 Mapping Entry 7 0x20560008
8 Mapping Entry 8 0x00000000
ServicePanel support the following Subindexes
0 Number of Entries 0
1 Mapping Entry 1 0x00000000
2 Mapping Entry 2 0x00000000
3 Mapping Entry 3 0x00000000
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
4.1.20.1 1A00h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Number
Valid Values 0x00 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 7
IL-E 7
MXIE 7
ServicePanel 0
4.1.20.2 1A00h Subindex 1 - Mapping Entry 1
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00000000 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x20400010
IL-E 0x20400010
MXIE 0x20400010
ServicePanel 0x00000000
4.1.20.3 1A00h Subindex 8 - Mapping Entry 8
Description
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00000000 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x00000000
IL-E 0x00000000
MXIE 0x00000000
ServicePanel 0x00000000

4.1.21 1A01h - Transmit PDO Mapping Parameter 2

Description
A Wilo Device will have this Transmit PDO preconfigured, It is recommended to use this pre configured configuration.
For more information see CiA Draft Standard 301, Version 4.02, page 112.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 3
1 Mapping Entry 1 0x20900020
2 Mapping Entry 2 0x208B0010
3 Mapping Entry 3 0x20A00010
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
IL-E support the following Subindexes
0 Number of Entries 2
1 Mapping Entry 1 0x20900020
2 Mapping Entry 2 0x208A0010
3 Mapping Entry 3 0x00000000
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
MXIE support the following Subindexes
0 Number of Entries 2
1 Mapping Entry 1 0x20900020
2 Mapping Entry 2 0x208A0010
3 Mapping Entry 3 0x00000000
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
ServicePanel support the following Subindexes
0 Number of Entries 0
1 Mapping Entry 1 0x00000000
2 Mapping Entry 2 0x00000000
3 Mapping Entry 3 0x00000000
4 Mapping Entry 4 0x00000000
5 Mapping Entry 5 0x00000000
6 Mapping Entry 6 0x00000000
7 Mapping Entry 7 0x00000000
8 Mapping Entry 8 0x00000000
4.1.21.1 1A01h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Number
Valid Values 0x00 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 3
IL-E 2
MXIE 2
ServicePanel 0
4.1.21.2 1A01h Subindex 1 - Mapping Entry 1
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00000000 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x20900020
IL-E 0x20900020
MXIE 0x20900020
ServicePanel 0x00000000
4.1.21.3 1A01h Subindex 8 - Mapping Entry 8
Description
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00000000 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x00000000
IL-E 0x00000000
MXIE 0x00000000
ServicePanel 0x00000000

4.1.22 1A02h - Transmit MPDO Mapping Parameter 3

Description
A Wilo Device will have this Transmit PDO preconfigured, It is recommended to use this pre configured configuration.
For more information see CiA Draft Standard 301, Version 4.02, page 112.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 0xFE
IL-E support the following Subindexes
0 Number of Entries 0xFE
MXIE support the following Subindexes
0 Number of Entries 0xFE
ServicePanel support the following Subindexes
0 Number of Entries 0xFE
4.1.22.1 1A02h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 0x00 to 0xFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0xFE
IL-E 0xFE
MXIE 0xFE
ServicePanel 0xFE

4.1.23 1FA0h - Object Scanner List

Description
It contains the mapping parameter for the MPDOs (configured with Par 1802h - Transmit MPDO Communication Parameter 3 and Par 1A02h - Transmit MPDO Mapping Parameter 3) the device is able to transmit. Sub-index 0 contains the number of mapped objects. All further entries define the data by its index, sub-index and length
For more information see CiA Draft Standard 301, Version 4.02, page 128.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries 8
1 Scanner Entry 1 0x01209201
2 Scanner Entry 2 0x01208700
3 Scanner Entry 3 0x01210100
4 Scanner Entry 4 0x01211300
5 Scanner Entry 5 0x00000000
6 Scanner Entry 6 0x00000000
7 Scanner Entry 7 0x00000000
8 Scanner Entry 8 0x00000000
IL-E support the following Subindexes
0 Number of Entries 8
1 Scanner Entry 1 0x01209201
2 Scanner Entry 2 0x01208700
3 Scanner Entry 3 0x01210100
4 Scanner Entry 4 0x01211300
5 Scanner Entry 5 0x00000000
6 Scanner Entry 6 0x00000000
7 Scanner Entry 7 0x00000000
8 Scanner Entry 8 0x00000000
MXIE support the following Subindexes
0 Number of Entries 8
1 Scanner Entry 1 0x01209201
2 Scanner Entry 2 0x01208700
3 Scanner Entry 3 0x01210100
4 Scanner Entry 4 0x01211300
5 Scanner Entry 5 0x00000000
6 Scanner Entry 6 0x00000000
7 Scanner Entry 7 0x00000000
8 Scanner Entry 8 0x00000000
ServicePanel support the following Subindexes
0 Number of Entries 8
1 Scanner Entry 1 0x00000000
2 Scanner Entry 2 0x00000000
3 Scanner Entry 3 0x00000000
4 Scanner Entry 4 0x00000000
5 Scanner Entry 5 0x00000000
6 Scanner Entry 6 0x00000000
7 Scanner Entry 7 0x00000000
8 Scanner Entry 8 0x00000000
4.1.23.1 1FA0h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no
Formatting Number
Valid Values 0x00 to 0xFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 8
IL-E 8
MXIE 8
ServicePanel 8
4.1.23.2 1FA0h Subindex 1 - Scanner Entry 1
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00000000 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x01209201
IL-E 0x01209201
MXIE 0x01209201
ServicePanel 0x00000000
4.1.23.3 1FA0h Subindex 8 - Scanner Entry 8
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Spec
Valid Values 0x00000000 to 0xFFFFFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x00000000
IL-E 0x00000000
MXIE 0x00000000
ServicePanel 0x00000000

4.2 Section Control

4.2.1 2000h - Setpoint (System)

Description
This Parameter sets the active working point of the pump. The resolution is in 0.01 Percent which means that the value 10000 corresponds to 100%. 100% represents the max setpoint (depending on Control Mode, Max Pressure, Max Speed, etc.) and 0% represents the setpoint 0 (not depending on control Mode).
If a value is written that is lower than the specified pump min value (depending on Control Mode) it is limited to the min value and the Par 2050h Bit 2 - Setpoint out of Range is set. The pump does not turn off if the value 0 is written.
The setpoint is saved internally on power off. If the pump is restarted or rebooted the last value is loaded automatically.
Usage
This value should not be automatically written, it should only be written if a change is required (a user manually changes the setpoint on a monitor or alike) otherwise it will take priority over other control methods, and would make it impossible to change the Setpoint from other sources. If an automated source is to set Values, then use Par 2008h - Bus Setpoint (System) instead of this Parameter.
This Parameter is write only, in order to read back the setpoint that is being processed by the pump, read Par 2048h - Selected Setpoint (System).
If a regulation or configuration mode is selected that depends solely on an external sensor, this Parameter is updated internally and cannot longer be written over the bus line. If this mode is changed the last setpoint from the sensor will be kept for the next regulation or configuration mode.
Dependency
This Parameter can change meaning if Par 2041h - Effective Control Mode (System) changes.
Dependency
This Parameter is disabled, if the Par 200Ah Bit 5 - Activate Bus Setpoint is set to "1".
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType SIGNED16
Volatile no, is saved on change
Formatting 0.01 Percent
Valid Values 0 to 10000
Error Value n/a
Access wo
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 5000
IL-E special default
The default value is the sum of 21AC and 21AD divided with 2.
MXIE 10000
ServicePanel no support

4.2.2 2001h - Control Mode (System)

Description
This Parameter sets the active control mode of the pump. It is basically the same as the Par 2009h - Bus Control Mode (System). If a Control Mode is to be set in the pump, this parameter should be used. This Parameter has no constant min and max values, instead it allows only the supported Control Modes to be written to This Parameter. If a value is written, that is not supported, a min, max or other suitable error will be generated by the pump and the last valid value will be kept.
If CONST_SPEED mode is set in a DP System, both pumps run syncronously.
The control mode is saved internally on power off. If the pump is restarted or rebooted the last value is loaded automatically.
Usage
This value should not be automatically written, it should only be written if a change is required (a user manually changes the setpoint on a monitor or alike) otherwise it will take priority over other control methods, and would make it impossible to change the Control Mode from other sources. If an automated source is to set values, then use Par 2009h - Bus Control Mode (System) instead of this Parameter. This value does not affect the value of Par 2000h - Setpoint (System) (or Par 2008h - Bus Setpoint (System)) and Par 2048h - Selected Setpoint (System) (if they already were at 50% they stay at 50% after changing this Parameter).
This Parameter is write only, in order to read back the chosen Control Mode for the pump, read Par 2049h - Selected Control Mode (System).
After changing this value, the Par 2000h - Setpoint (System) should be written as well to make sure that the correct setpoint is set for the new regulation mode.If Par 2316h - Pump Housing is set to Y-Branch Pump Housing, it is not possible to select Control Mode dp-v.
Dependency
This Parameter is disabled, if the Par 200Ah Bit 6 - Activate Bus Control Mode is set to "1".
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Dependency
This Parameter disables Par 208Bh - Estimated Pressure (System), if it is set to "CONST_CONTROL (PID)".
Dependency
This Parameter disables Par 208Ch - Estimated Pressure Range Min (System), if it is set to "CONST_CONTROL (PID)".
Dependency
This Parameter disables Par 208Dh - Estimated Pressure Range Max (System), if it is set to "CONST_CONTROL (PID)".
Value Description
Value Description
0 CONST_SPEED (n-c)
1 CONST_FREQ
2 CONST_POWER
3 CONST_HEAD
4 CONST_PRESSURE (p-c)
5 CONST_DIFFPRESS (dp-c)
6 VAR_DIFFPRESS (dp-v)
7 CONST_FLOW
8 CONST_TEMP
9 CONST_TEMPDIFF
10 CONST_LEV
11 TEMP_VARIABLE (dp-c=f(T))
12 CONST_CONTROL (PID)
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 12
Error Value n/a
Access wo
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 6
supports only the values 0, 5, 6, 11.
IL-E 5
supports only the values 0, 5, 6, 12.
MXIE 0
supports only the values 0, 4, 12.
ServicePanel no support

4.2.3 2002h - Command (System)

Description
This Parameter controls the running mode of the pump.
Usage
This value should not be automatically written, it should only be written if a change is required (a user manually changes the setpoint on a monitor or alike) otherwise it will take priority over other control methods, and would make it impossible to turn the pump on or off from other sources. If an automated source is to set values, then use Par 200Ah - Bus Command (System) instead of this Parameter.
Dependency
This Parameter is disabled, if the Par 200Ah Bit 5 - Activate Bus Setpoint is set to "1".
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Bitset Description
Bit Bit equals Zero Bit equals One
Pump Off  Pump On 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access wo
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0x01
IL-E 0x01
MXIE 0x01
ServicePanel no support
4.2.3.1 2002h Bit 0 - Pump On/Off
Description
This Bit turns the pump on or off. On means that the pump is pumping and Off means that the pump is not pumping. It is not possible to completely turn off the pump, the pump is always in standby mode.
The on off setting is saved internally on power off, this parameter becomes this saved value upon restart or reboot.
Dependency
This Bit has the same priority as Par 200Ah Bit 0 - Pump On/Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 2 - Extern Max.
Dependency
This Bit has lower priority than Par 200Ah Bit 3 - Extern Min.
Dependency
This Bit has lower priority than Par 200Ah Bit 4 - Extern On.
Device Support and Default Value
SupportDefault
Stratos 1
IL-E 1
MXIE 1
ServicePanel no support

4.2.4 2008h - Bus Setpoint (System)

Description
This Parameter sets the active working point of the pump.
Usage
This value should only be used if a source continuously sends values (a regulation unit, a 0-10V conversion unit or similar). If only a new value is to be written, then use Par 2000h - Setpoint (System).
If the setpoint is accompanied with a control mode (PDO), and the control mode is invalid, only the setpoint will be accepted and it would then depend on the previously selected control mode.
This Parameter is write only, in order to read back the setpoint that is being processed by the pump, read Par 2048h - Selected Setpoint (System).
All percentages lower than the current min value (depending on Control Mode) are accepted, but limits the value to the min value. This activates the Par 2050h Bit 2 - Setpoint out of Range. The pump does not turn off if the value 0 is written to This Parameter.
This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.
In the case of a DP or multipump where one or more pumps are set to Off, Max, Min or On, the other (DP), or one of the others (MP), still regulates with the chosen setpoint (This Parameter). This means that an external regulation unit can set specific pumps to Off, Max, Min or On (with specified fixed speed) and still regulate the last pump externally.
Dependency
This Parameter can change meaning if Par 2041h - Effective Control Mode (System) changes.
Dependency
This Parameter is disabled, if the Par 200Ah Bit 5 - Activate Bus Setpoint is set to "0".
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType SIGNED16
Volatile no, is saved on change
Formatting 0.01 Percent
Valid Values 0 to 10000
Error Value n/a
Access wo
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos 5000
IL-E special default
The default value is the sum of 21AC and 21AD divided with 2.
MXIE 10000
ServicePanel no support

4.2.5 2009h - Bus Control Mode (System)

Description
This Parameter is basically the same as the Par 2001h - Control Mode (System). The difference is that this parameter is written by a I/O-Module and it can have a higher priority (set by Par 200Ah Bit 6 - Activate Bus Control Mode) than its counterpart. It sets the active control mode of the pump.
Usage
This value should only be used if a source continuously sends values (a regulation unit, a 0-10V conversion unit or similar). If only a new value is to be written, then use Par 2001h - Control Mode (System).
This Parameter is write only, in order to read back the chosen setpoint for the pump, read Par 2049h - Selected Control Mode (System).
This Parameter has no constant min and max values, instead it allows only the supported Control Modes to be written to This Parameter. If a value is written, that is not supported, a min, max or other suitable error will be generated by the pump.
This Parameter is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.
If CONST_SPEED mode is set in a DP System, both pumps run syncronously.
Dependency
This Parameter is disabled, if the Par 200Ah Bit 6 - Activate Bus Control Mode is set to "0".
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Dependency
This Parameter disables Par 208Bh - Estimated Pressure (System), if it is set to "CONST_CONTROL (PID)".
Value Description
Value Description
0 CONST_SPEED (n-c)
1 CONST_FREQ
2 CONST_POWER
3 CONST_HEAD
4 CONST_PRESSURE (p-c)
5 CONST_DIFFPRESS (dp-c)
6 VAR_DIFFPRESS (dp-v)
7 CONST_FLOW
8 CONST_TEMP
9 CONST_TEMPDIFF
10 CONST_LEV
11 TEMP_VARIABLE (dp-c=f(T))
12 CONST_CONTROL (PID)
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 12
Error Value n/a
Access wo
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos 6
supports only the values 0, 5, 6, 11.
IL-E 5
supports only the values 0, 5, 6, 12.
MXIE 0
supports only the values 0, 4, 12.
ServicePanel no support

4.2.6 200Ah - Bus Command (System)

This Parameter is write only, in order to read back the chosen setpoint for the pump, some of the values can be read in Par 204Ah - Selected Command (System).
This Parameter is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.
The activation bits are always evaluated first, so this byte can contain an combination of different values.
This Parameter is deactivated if Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module) is activated and no corresponding heartbeat is present on the bus.
Example
If Par 200Ah Bit 2 - Extern Max is set in an MP system, then all pumps would run at Maximum Speed. If Par 2323h Bit 2 - is set at the same time, all pumps would run at Maximum Speed, but Slave 2, since Member Enable (Extern Off) has higher Priority than Extern Max, would be turned off.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Bitset Description
Bit Bit equals Zero Bit equals One
Pump Off  Pump On 
No Influence  Pump Off Override 
No Influence  Pump Max Override 
No Influence  Pump Min Override 
No Influence  Pump On Override 
Activate P2000  Activate P2008 
Activate P2001  Activate P2009 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access wo
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos 0x01
IL-E 0x01
MXIE 0x01
ServicePanel no support
4.2.6.1 200Ah Bit 0 - Pump On/Off
Description
This Bit turns the pump on or off. On means that the pump is pumping and Off means that the pump is not pumping. It is not possible to completely turn off the pump, the pump is always in standby mode.
Usage
This value should only be used if a source continuously sends values (a regulation unit, a 0-10V conversion unit or similar). If only a new value is to be written, then use Par 2002h Bit 0 - Pump On/Off.
The effective value in the pump is saved with power off (non-volatile).
This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.
Dependency
This Bit has the same priority as Par 2002h Bit 0 - Pump On/Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 2 - Extern Max.
Dependency
This Bit has lower priority than Par 200Ah Bit 3 - Extern Min.
Dependency
This Bit has lower priority than Par 200Ah Bit 4 - Extern On.
Dependency
This Bit has partially lower priority than Par 2022h - Extern Max (DP/MP).
Dependency
This Bit has partially lower priority than Par 2024h - Extern Min (DP/MP).
Dependency
This Bit has partially lower priority than Par 2026h - Extern Fixed On (DP/MP).
Dependency
This Bit has partially lower priority than Par 2323h - Member Pump Enable.
Dependency
This Bit is disabled, if the Par 200Ah Bit 5 - Activate Bus Setpoint is set to "0".
Dependency
CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Device Support and Default Value
SupportDefault
Stratos 1
IL-E 1
MXIE 1
ServicePanel no support
4.2.6.2 200Ah Bit 1 - Extern Off
Description
This Bit turns the pump off, disregarding the previous setting (also see priority dependencies below).
Usage
This value should only be used if a source continuously sends values (a regulation unit). If this functionality is required, without having a regulation source then you can mimic this Parameter by setting Par 2002h Bit 0 - Pump On/Off to 0.
This Subindex must not be saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.
This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.
See Par 200Ah - Bus Command (System) for an Priority example.
It is only possible to write or modify this bit if an I/O Module (or gateway, depending on Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module)) is sending Heartbeats on the configured address. If this Heartbeat is lost this Parameter is set to 0 (However the pump stays Off).
If this variable is set, it is also displayed in the Old IR-Monitor.
Dependency
This Bit has higher priority than Par 200Ah Bit 0 - Pump On/Off.
Dependency
This Bit has higher priority than Par 200Ah Bit 2 - Extern Max.
Dependency
This Bit has higher priority than Par 200Ah Bit 3 - Extern Min.
Dependency
This Bit has higher priority than Par 200Ah Bit 4 - Extern On.
Dependency
This Bit has higher priority than Par 2022h - Extern Max (DP/MP).
Dependency
This Bit has higher priority than Par 2024h - Extern Min (DP/MP).
Dependency
This Bit has higher priority than Par 2026h - Extern Fixed On (DP/MP).
Dependency
This Bit has higher priority than Par 2323h - Member Pump Enable.
Dependency
CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel no support
4.2.6.3 200Ah Bit 2 - Extern Max
Description
This Bit makes the pump run at maximum speed, disregarding the previous setting (also see priority dependencies below).
Usage
This value should only be used if a source continuously sends values (a regulation unit). If this functionality is required, without having a regulation source then you can mimic this Parameter by first setting the Par 2000h - Setpoint (System) to 100% and then Par 2001h - Control Mode (System) to Speed mode. To disable this mimic, first write the old value to Par 2001h - Control Mode (System) then the old value to Par 2000h - Setpoint (System).
This Subindex must not be saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.
This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.
See Par 200Ah - Bus Command (System) for an Priority example.
It is only possible to write or modify this bit if an I/O Module (or gateway, depending on Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module)) is sending Heartbeats on the configured address. If this Heartbeat is lost this Parameter is set to 0.
Dependency
This Bit has higher priority than Par 200Ah Bit 0 - Pump On/Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.
Dependency
This Bit has higher priority than Par 200Ah Bit 3 - Extern Min.
Dependency
This Bit has higher priority than Par 200Ah Bit 4 - Extern On.
Dependency
This Bit has higher priority than Par 2022h - Extern Max (DP/MP).
Dependency
This Bit has higher priority than Par 2024h - Extern Min (DP/MP).
Dependency
This Bit has higher priority than Par 2026h - Extern Fixed On (DP/MP).
Dependency
This Bit has partially lower priority than Par 2323h - Member Pump Enable.
Dependency
CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel no support
4.2.6.4 200Ah Bit 3 - Extern Min
Description
This Bit makes the pump run at minimum speed, disregarding the previous setting (also see priority dependencies below).
Usage
This value should only be used if a source continuously sends values (a regulation unit). If this functionality is required, without having a regulation source then you can mimic this Parameter by first setting the Par 2000h - Setpoint (System) to 0% and then Par 2001h - Control Mode (System) to Speed mode. To disable this mimic, first write the old value to Par 2001h - Control Mode (System) then the old value to Par 2000h - Setpoint (System).
This Subindex must not be saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.
This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.
See Par 200Ah - Bus Command (System) for an Priority example.
The Extern Min function reduces the speed of the pump to a level where a minimal function is guaranteed. It does not always correspond to the min speed value.
It is only possible to write or modify this bit if an I/O Module (or gateway, depending on Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module)) is sending Heartbeats on the configured address. If this Heartbeat is lost this Parameter is set to 0.
Dependency
This Bit has higher priority than Par 200Ah Bit 0 - Pump On/Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 2 - Extern Max.
Dependency
This Bit has higher priority than Par 200Ah Bit 4 - Extern On.
Dependency
This Bit has partially lower priority than Par 2022h - Extern Max (DP/MP).
Dependency
This Bit has higher priority than Par 2024h - Extern Min (DP/MP).
Dependency
This Bit has higher priority than Par 2026h - Extern Fixed On (DP/MP).
Dependency
This Bit has partially lower priority than Par 2323h - Member Pump Enable.
Dependency
CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel no support
4.2.6.5 200Ah Bit 4 - Extern On
Description
This Bit turns the pump on, disregarding the previous setting (also see priority dependencies below).
Usage
This value should only be used if a source continuously sends values (a regulation unit). If this functionality is required, without having a regulation source then you can mimic this Parameter by setting Par 2002h Bit 0 - Pump On/Off to 1.
This Subindex must not be saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.
This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.
See Par 200Ah - Bus Command (System) for an Priority example.
It is only possible to write or modify this bit if an I/O Module (or gateway, depending on Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module)) is sending Heartbeats on the configured address. If this Heartbeat is lost this Parameter is set to 0.
Dependency
This Bit has higher priority than Par 200Ah Bit 0 - Pump On/Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.
Dependency
This Bit has lower priority than Par 200Ah Bit 2 - Extern Max.
Dependency
This Bit has lower priority than Par 200Ah Bit 3 - Extern Min.
Dependency
This Bit has partially lower priority than Par 2022h - Extern Max (DP/MP).
Dependency
This Bit has partially lower priority than Par 2024h - Extern Min (DP/MP).
Dependency
This Bit has higher priority than Par 2026h - Extern Fixed On (DP/MP).
Dependency
This Bit has partially lower priority than Par 2323h - Member Pump Enable.
Dependency
CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel no support
4.2.6.6 200Ah Bit 5 - Activate Bus Setpoint
Description
This Bit activates the setpoint and the on off setting over the bus.
This Subindex is not saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.
This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Bus Regulation device.
To read the status of this bit, use Par 2056h Bit 2 - Bus Setpoint Active.
This Subindex is disabled if Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module) is activated and no corresponding heartbeat is present on the bus.
Dependency
CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Dependency
This Bit disables Par 2000h - Setpoint (System), if it is set to "1".
Dependency
This Bit disables Par 2008h - Bus Setpoint (System), if it is set to "0".
Dependency
This Bit disables Par 2002h Bit 0 - Pump On/Off, if it is set to "1".
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel no support
4.2.6.7 200Ah Bit 6 - Activate Bus Control Mode
Description
This Bit activates the Control Mode over the bus.
This Subindex is not saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.
This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Bus Regulation device.
To read the status of this bit, use Par 2056h Bit 3 - Bus Control Mode Active.
This Subindex is disabled if Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module) is activated and no corresponding heartbeat is present on the bus.
Dependency
CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Dependency
This Bit disables Par 2001h - Control Mode (System), if it is set to "1".
Dependency
This Bit disables Par 2009h - Bus Control Mode (System), if it is set to "0".
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 0
MXIE 0
ServicePanel no support

4.3 Section Status

4.3.1 2040h - Effective Capacity (System)

Description
This Parameter contains the effective value of the pump, at which it works in this moment, in percent. This value is usually very close to Par 2048h - Selected Setpoint (System). This value is relative to Par 2041h - Effective Control Mode (System). 100% represents the max value for the chosen control mode (as described in Par 2000h - Setpoint (System)).
In the case of a Double- or Multi-Pump System, This Parameter is a System Parameter, it always represents data for the complete Double- or Multi-Pump System.
In the case of a DP or MP System it contains the speed of the active running pump(s), and if CONST_SPEED, together with two pumps running at a different speeds, it contains the Error Value.
Revision History
(1.01) The effective value in dp-v is now depending on the current flow, this means that the effective value can be between 50% and 100% of the wanted setpoint.
Dependency
This Parameter can change meaning if Par 2041h - Effective Control Mode (System) changes.
Parameter Specification
Specification
VariableType SIGNED16
Volatile yes
Formatting 0.01 Percent
Valid Values 0x8000 to 0x7FFF
Error Value 0x7FFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.2 2041h - Effective Control Mode (System)

Description
This Parameter contains the effective regulation mode. see Pump Control Mode for the regulation modes. For a list of modes see Par 2001h - Control Mode (System).
The effective values in the pump are saved with power off (non-volatile).
the value must represent one of the supported control modes.
In the case of a Double- or Multi-Pump System, This Parameter is a System Parameter, it always represents data for the complete Double- or Multi-Pump System.
Dependency
This Parameter can change if Par 2049h - Selected Control Mode (System) changes.
Value Description
Value Description
0 CONST_SPEED (n-c)
1 CONST_FREQ
2 CONST_POWER
3 CONST_HEAD
4 CONST_PRESSURE (p-c)
5 CONST_DIFFPRESS (dp-c)
6 VAR_DIFFPRESS (dp-v)
7 CONST_FLOW
8 CONST_TEMP
9 CONST_TEMPDIFF
10 CONST_LEV
11 TEMP_VARIABLE (dp-c=f(T))
12 CONST_CONTROL (PID)
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Select
Valid Values 0 to 0xFF
Error Value 0xFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.3 2042h - Effective Command (System)

Description
This Parameter contains the effective values that has been acceped by the pump, or in the case of an DP/MP System, all pumps. This means that in a Single Pump, only one bit can be active at any one time. In a DP or MP Pump more bits can be active if the members have different bits set.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.3.1 2042h Bit 0 - Pump On/Off
Description
This Bit shows if the pump (or at least one of the pumps from the System) is turned on with the on/off bit (no extern values). This means that if at least one pump of the system is pumping without having the bit extern max, extern min or extern on set, this bit is set.
If this bit reports only if the pump is activated for pumping not that it is actually pumping, see Pump Kick and Zero Flow. To see if all pumps are stopped or pumping please use Par 2052h Bit 1 - Pump is Operating.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.3.2 2042h Bit 1 - Extern Off
Description
This Bit shows if the pump has been turned off with an Extern Off function. This bit is active when one or more of all Extern Off functions in the pump is active. It does not activate if only the pump is turned off with the Pump On/Off parameter.
This bit contains the value '1' if at least one pump in the DP or MP System is stopped by Extern Off.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.3.3 2042h Bit 2 - Extern Max
Description
This Bit shows if the pump has been set to run at maximum speed with an Extern Max function. This bit is active when one or more of all Extern Max functions in the pump is active. It does not activate if only the pump is set to max with the normal setpoint parameter.
This bit contains the value '1' if at least one pump in the DP or MP System is running in Extern Max.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.3.4 2042h Bit 3 - Extern Min
Description
This Bit shows if the pump has been set to run at minimum speed with an Extern Min function. This bit is active when one or more of all Extern Min functions in the pump is active. It does not activate if only the pump is set to min with the normal setpoint parameter.
This bit contains the value '1' if at least one pump in the DP or MP System is running in Extern Min.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.3.5 2042h Bit 4 - Extern On
Description
This Bit shows if the pump has been turned on with an Extern On function. This bit is active when one or more of all Extern On functions in the pump is active. It does not activate if only the pump is turned on with the Pump On/Off parameter.
This bit contains the value '1' if at least one pump in the DP or MP System is running in Extern On.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.4 2048h - Selected Setpoint (System)

Description
This Parameter contains the last accepted setpoint from Par 2000h - Setpoint (System) and setpoint from the Pump Menu or Par 2008h - Bus Setpoint (System) (depending on Par 200Ah Bit 5 - Activate Bus Setpoint). This Parameters value is valid for the Regulation Mode stored in Par 2049h - Selected Control Mode (System). If a regulation or configuration mode is selected that depends solely on an external sensor, this Parameter is updated internally to reflect the setpoint of this mode. If this mode is changed the last setpoint will be kept for the next regulation or configuration mode.
This value is the same value that is displayed in the pump display.
Dependency
This Parameter can change meaning if Par 2041h - Effective Control Mode (System) changes.
Parameter Specification
Specification
VariableType SIGNED16
Volatile yes
Formatting 0.01 Percent
Valid Values 0x8000 to 0x7FFF
Error Value 0x7FFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.5 2049h - Selected Control Mode (System)

Description
This Parameter contains the last accepted Control Mode from Par 2001h - Control Mode (System) and the Control Mode item from the Pump Display or Par 2009h - Bus Control Mode (System) (depending on Par 200Ah Bit 6 - Activate Bus Control Mode).
Dependency
This Parameter can change if Par 2001h - Control Mode (System) changes.
Dependency
This Parameter can change if Par 2009h - Bus Control Mode (System) changes.
Dependency
This Parameter can change source if Par 200Ah Bit 5 - Activate Bus Setpoint changes.
Dependency
This Parameter can change source if Par 200Ah Bit 6 - Activate Bus Control Mode changes.
Value Description
Value Description
0 CONST_SPEED (n-c)
1 CONST_FREQ
2 CONST_POWER
3 CONST_HEAD
4 CONST_PRESSURE (p-c)
5 CONST_DIFFPRESS (dp-c)
6 VAR_DIFFPRESS (dp-v)
7 CONST_FLOW
8 CONST_TEMP
9 CONST_TEMPDIFF
10 CONST_LEV
11 TEMP_VARIABLE (dp-c=f(T))
12 CONST_CONTROL (PID)
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Select
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.6 204Ah - Selected Command (System)

Description
This Parameter contains the last accepted Pump Command from Par 2002h - Command (System) and the On/Off item from the Pump Display or Par 200Ah - Bus Command (System) (depending on Par 200Ah Bit 5 - Activate Bus Setpoint).
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.6.1 204Ah Bit 0 - Pump On/Off
Description
This Bit is a representation of the selectable global on bit and it shows if the pump (or System) should be turned on or off. On means that at least one pump should be on (it stays on even if a higher priorized source has turned the pump off). Off means that the pump system should not pump (it stays off even if a higher priorized source has turned the pump on). This bit can be used as a read back bit in order to see if the user has turned the pump on.
If the pump is set to On, but Extern Off is active this Parameter would show On.
Pumps can be running even if this Parameter shows Off!
This Subindex contains the value '1' if the pump on/off command has been set to On.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.6.2 204Ah Bit 1 - Extern Off
Description
This Bit shows if the pump has been turned off with an Extern Off function.
This Subindex contains the value '1' if at least one extern off function has been activated.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.6.3 204Ah Bit 2 - Extern Max
Description
This Bit shows if the pump has been set to run at maximum speed with an Extern Max function.
This Subindex contains the value '1' if at least one extern max function has been activated.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.6.4 204Ah Bit 3 - Extern Min
Description
This Bit shows if the pump has been set to run at minimum speed with an Extern Min function.
This Subindex contains the value '1' if at least one extern min function has been activated.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.6.5 204Ah Bit 4 - Extern On
Description
This Bit shows if the pump has been turned on with an Extern On function.
This Subindex contains the value '1' if at least one extern on function has been activated.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.7 2050h - Controller Status (System)

Description
This parameter returns regulation information from the Pump or System.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.7.1 2050h Bit 0 - Lower Regulation Limit
Description
This Bit contains status over the Lower Regulation Limit (pump is running at min speed).
In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps. Extern Multipump regulators will know the current speed of the slave pumps and its min and max values, so this bit is superfluous.
This Subindex is '1' if the DP or MP System is operating at the lowest possible operation point.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.7.2 2050h Bit 1 - Upper Regulation Limit
Description
This Bit contains status over the Upper Regulation Limit (pump is running at max speed, or max possible power).
In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps. Extern Multipump regulators will know the current speed of the slave pumps and its min and max values, so this bit is superfluous.
This Subindex is '1' if the DP or MP System is operating with the highest possible speed or power.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.7.3 2050h Bit 2 - Setpoint out of Range
Description
This Bit contains '1' if the last setpoint was out of range (if setpoint was smaller than min for the selected control mode).
Since the Min value will change dependent on Pump type and capacity, this parameter adapts to Single, Double or Multi Pump changes automatically.
In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps. Extern Multipump regulators will know the current speed of the slave pumps, so this bit is superfluous.
DP-MP, This Subindex is '1' if the setpoint (in the Master) is set to a value below the specified min-value (for the current operation mode).
Dependency
This Bit can change if Par 2041h - Effective Control Mode (System) changes.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.7.4 2050h Bit 3 - Setpoint Difference (>10%)
Description
This Bit contains if the setpoint ( P2000h / P2008h ) and Actual Value ( P2040h ) difference is larger than 10% (<±10%).
In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps. Extern Multipump regulators will know the current speed of the slave pumps, so this bit is superfluous.
DP-MP, This Subindex is '1' if the setpoint (in the Master) differs with more than 10% from the Actual Value.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.7.5 2050h Bit 4 - Q not Computable
Description
This Bit contains if Flow (Q) is not computable.
In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps.
This Subindex is '1' if the DP or MP System is in a position where it cannot calculate the flow.
Device Support and Default Value
SupportDefault
Stratos no default
supports only the values 0.
IL-E special default
It depends on the chosen Control Mode
MXIE no default
supports only the values 1.
ServicePanel no support
4.3.7.6 2050h Bit 5 - H not Computable
Description
This Bit contains if Pressure (H) is not computable.
In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps.
This Subindex is '1' if the DP or MP System is in a position where it cannot calculate the pressure.
Device Support and Default Value
SupportDefault
Stratos no default
supports only the values 0.
IL-E no default
MXIE no default
ServicePanel no support
4.3.7.7 2050h Bit 6 - Auto Night Active
Description
This Bit contains if Auto Night is active or not. If the pump does not support this, it is always 0.
In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.3.8 2052h - Operation Status (System)

Description
This Parameter describes the current Operation Status, if the pump is ready, if error is present and so on. All these bits are System wide (DP or MP) if pump specific (Master or Slave) values are wanted please see Par 2058h - Ready for Operation (DP/MP), Par 205Ah - Pump is Operating (DP/MP), Par 205Ch - Service Required (DP/MP), Par 205Eh - Warning Present (DP/MP), Par 2060h - Error Present (DP/MP) and Par 2062h - Final Error Present (DP/MP).
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.8.1 2052h Bit 0 - Ready for Operation
Description
This Bit contains the Ready for Operation status for the Single Pump or in the case of a DP or MP System, for the Complete System. If at least one Pump is Ready for Operation in the System, this bit is set. Ready for Operation means that the pump will start as soon as it is turned on (power, no error, not disabled and no extern off).
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.8.2 2052h Bit 1 - Pump is Operating
Description
This Bit contains if the pump is operating. In the case of a DP or MP System, this bit is set if at least one Pump is operating. Operating means that the pump rotates.
A pumpkick also makes this flag turn on. If Zero Flow is active, the pump does not rotate and this flag is off.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.8.3 2052h Bit 2 - Service Required
Description
This Bit contains a '1' if Service is required for this pump or in the case of a DP or MP System, If at least one Pump requires Service. The service required information can be set together with a warning or an error. If it is set alone, it is usually an indication that it is time for service (parts exchange or similar). If it is set together with a warning or an error is indicates that this warning or error can only be resetted by someone at the pump, and not remotely or by itself.
This Subindex is set together with some errors (See Wilo LON spec EBA_8120_10).
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.8.4 2052h Bit 3 - Warning Present
Description
This Bit contains a '1' if a Warning is present in this pump or in the case of a DP or MP System, If at least one Pump has a Warning present. A warning means that something unwanted has happened but the motor still runs.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.8.5 2052h Bit 4 - Error Present
Description
This Bit contains a '1' if an Error is present in this pump or in the case of a DP or MP System, If at least one Pump has an Error present. An Error means that something unwanted has happened and the motor has turned off.
An Error is sent when it occurs.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.8.6 2052h Bit 5 - Final Error
Description
This Bit contains a '1' if the Final Error Status has been reached (error is present in this pump or DP/MP System).
A Final Error is usually sent when the sixth Error occurs. Also see Par 2207h - HV/AC System Error Detection.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.3.9 2054h - Bus Status

Description
This parameter describes what protocols and protocol modes are active.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.9.1 2054h Bit 0 - Bus Connected
Description
This Bit is '1' if CAN is Connected (IF-CAN inserted and heartbeat on bus present)
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.9.2 2054h Bit 1 - Module Auto Safety Active
Description
This Bit is '1' if the Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module) is set to the default value (I/O Module Safety function is turned on and the address is set to the correct offset). It is basically a status flag to see if the heartbeat check is activated and unchanged, it is used by regulation units to see if they can pair up with this pump.
A bit for the I/O-Module, so that it recognices if it is allowed to engage a connection to this pump.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.9.3 2054h Bit 2 - Wink Service
Description
If the menuitem "ID" in the device menu is activated, this bit is set to 1 for 6 seconds.
Usage
In a Pure CANopen network you can check the address of the Pump in order to identify the pump in a network. However if you have several CANopen subnets and all are connected to all larger network, you can set this wink bit and so uniquely identify a single pump in the main BMS controller.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.9.4 2054h Bit 3 - External Sensor Active
Description
This Bit is set if an external sensor is used in the regulation loop. This Sensor can be connected over LON or CAN.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.9.5 2054h Bit 5 - Module Auto Safety In Use
Description
This Bit is set if a heartbeat is present on the address specified in Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module). It used to see if the active regulation is activated (possible to set Par 200Ah - Bus Command (System) bits 1 through 6).
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.9.6 2054h Bit 6 - User Menu Open
Description
This Bit is set if a user has opened the device menu or is browsing the device with an IR-Monitor.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.3.10 2056h - Control Status

Description
This Parameter returns control status information. All sources that can override the bus are listed here. If one of them temporarily or permamently takes control the corresponding bit is set high.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.10.1 2056h Bit 0 - LON/PLR Controlled
Description
This Bit is '1' if LON/PLR is Connected (IF-LON/PLR inserted, the first message has been received and no timeout). This means that it is not possible to change values locally.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.10.2 2056h Bit 1 - Bus Clamps Active
Description
If the Gateway or I/O-Module has activated one of the parameters Par 200Ah Bit 1 - Extern Off to Par 200Ah Bit 4 - Extern On then this bit is set. It means that extern clamps are affecting the system so it might not behave as expected.
In the case of an DP or MP Pump, this bit is set if at least one of the pumps behave as described above.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.10.3 2056h Bit 2 - Bus Setpoint Active
Description
If the Gateway or I/O-Module has activated the parameter Par 200Ah Bit 5 - Activate Bus Setpoint then this bit is set. It means that part of the Regulation control has been activated and that some control values might not possible to change.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.10.4 2056h Bit 3 - Bus Control Mode Active
Description
If the Gateway or I/O-Module has activated the parameter Par 200Ah Bit 6 - Activate Bus Control Mode then this bit is set. It means that part of the Regulation control has been activated and that some control values might not possible to change.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.10.5 2056h Bit 4 - Local Operation Active
Description
If the IR-Monitor or IR-Modul has activated the Local Operation mode (local access only), then this Parameter is set.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.10.6 2056h Bit 5 - Pump Clamps Active
Description
If one or more of the local Clamps (on the module itself or directly on an inserted IF-Module) on the Pump has been activated, this bit is set. It means that some control values might not possible to change. The relays (SBM, SSM) are no clamps and are not signalled here.
In the case of an DP or MP Pump, this bit is set if at least one of the pumps behave as described above.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.10.7 2056h Bit 6 - External Setpoint Active
Description
This Bit is set if the Par 2235h - External Setpoint Signal Type is set and the Master uses this external value as a setpoint value.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.10.8 2056h Bit 7 - Internally Controlled
Description
This Bit is set if the pump internally sets values. Pump Kick, Auto Night Mode and Zero Flow Detection Modifies this bit. It is also set if an Error (or specific test) is active that affects the operation of the pump.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.11 2058h - Ready for Operation (DP/MP)

Description
This Parameter describes the current Operation Status for a specific member of this System (DP or MP). If a System wide status is wanted please use Par 2052h Bit 0 - Ready for Operation. More information about what is displayed here can also be found at Par 2052h Bit 0 - Ready for Operation.
Bitset Description
Bit Bit equals Zero Bit equals One
no Ready for Operation (Master)  Ready for Operation (Master) 
no Ready for Operation (Slave 1)  Ready for Operation (Slave 1) 
no Ready for Operation (Slave 2)  Ready for Operation (Slave 2) 
no Ready for Operation (Slave 3)  Ready for Operation (Slave 3) 
no Ready for Operation (Slave 4)  Ready for Operation (Slave 4) 
no Ready for Operation (Slave 5)  Ready for Operation (Slave 5) 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.12 205Ah - Pump is Operating (DP/MP)

Description
This Parameter describes the current Operation Status for a specific member of this System (DP or MP). If a System wide status is wanted please use Par 2052h Bit 1 - Pump is Operating. More information about what is displayed here can also be found at Par 2052h Bit 1 - Pump is Operating.
Bitset Description
Bit Bit equals Zero Bit equals One
no Pump is Operating (Master)  Pump is Operating (Master) 
no Pump is Operating (Slave 1)  Pump is Operating (Slave 1) 
no Pump is Operating (Slave 2)  Pump is Operating (Slave 2) 
no Pump is Operating (Slave 3)  Pump is Operating (Slave 3) 
no Pump is Operating (Slave 4)  Pump is Operating (Slave 4) 
no Pump is Operating (Slave 5)  Pump is Operating (Slave 5) 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.13 205Ch - Service Required (DP/MP)

Description
This Parameter describes the current Operation Status for a specific member of this System (DP or MP). If a System wide status is wanted please use Par 2052h Bit 2 - Service Required. More information about what is displayed here can also be found at Par 2052h Bit 2 - Service Required.
Bitset Description
Bit Bit equals Zero Bit equals One
no Service Required (Master)  Service Required (Master) 
no Service Required (Slave 1)  Service Required (Slave 1) 
no Service Required (Slave 2)  Service Required (Slave 2) 
no Service Required (Slave 3)  Service Required (Slave 3) 
no Service Required (Slave 4)  Service Required (Slave 4) 
no Service Required (Slave 5)  Service Required (Slave 5) 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.14 205Eh - Warning Present (DP/MP)

Description
This Parameter describes the current Operation Status for a specific member of this System (DP or MP). If a System wide status is wanted please use Par 2052h Bit 3 - Warning Present. More information about what is displayed here can also be found at Par 2052h Bit 3 - Warning Present.
Bitset Description
Bit Bit equals Zero Bit equals One
no Warning Present (Master)  Warning Present (Master) 
no Warning Present (Slave 1)  Warning Present (Slave 1) 
no Warning Present (Slave 2)  Warning Present (Slave 2) 
no Warning Present (Slave 3)  Warning Present (Slave 3) 
no Warning Present (Slave 4)  Warning Present (Slave 4) 
no Warning Present (Slave 5)  Warning Present (Slave 5) 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.15 2060h - Error Present (DP/MP)

Description
This Parameter describes the current Operation Status for a specific member of this System (DP or MP). If a System wide status is wanted please use Par 2052h Bit 4 - Error Present. More information about what is displayed here can also be found at Par 2052h Bit 4 - Error Present.
Bitset Description
Bit Bit equals Zero Bit equals One
no Error Present (Master)  Error Present (Master) 
no Error Present (Slave 1)  Error Present (Slave 1) 
no Error Present (Slave 2)  Error Present (Slave 2) 
no Error Present (Slave 3)  Error Present (Slave 3) 
no Error Present (Slave 4)  Error Present (Slave 4) 
no Error Present (Slave 5)  Error Present (Slave 5) 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.16 2062h - Final Error Present (DP/MP)

Description
This Parameter describes the current Operation Status for a specific member of this System (DP or MP). If a System wide status is wanted please use Par 2052h Bit 5 - Final Error. More information about what is displayed here can also be found at Par 2052h Bit 5 - Final Error.
Bitset Description
Bit Bit equals Zero Bit equals One
no Final Error Present (Master)  Final Error Present (Master) 
no Final Error Present (Slave 1)  Final Error Present (Slave 1) 
no Final Error Present (Slave 2)  Final Error Present (Slave 2) 
no Final Error Present (Slave 3)  Final Error Present (Slave 3) 
no Final Error Present (Slave 4)  Final Error Present (Slave 4) 
no Final Error Present (Slave 5)  Final Error Present (Slave 5) 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.17 2064h - Rotating Direction (System)

Description
This Subindex contains the Rotating Direction of all pumps in this system. If you stand behind the motor (where you can see the ventilator blades of the motor), then 1 is Anti-Clockwise (in PLR notated as Left) and 0 is Clockwise (in PLR notated as Right). If you follow the IEC 60034-8 Standard, then 1 equals Clockwise and 0 equals Anti-Clockwise.
Bitset Description
Bit Bit equals Zero Bit equals One
Rotating Direction (Single Pump or Master) Right  Left 
Rotating Direction (Slave 1) Right  Left 
Rotating Direction (Slave 2) Right  Left 
Rotating Direction (Slave 3) Right  Left 
Rotating Direction (Slave 4) Right  Left 
Rotating Direction (Slave 5) Right  Left 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 1
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.3.18 206Dh - Base Load Pump

Description
This parameter contains the pump that is currently running as Base Load. This can be changed with Par 2320h - Pump Swap Event.
Value Description
Value Description
0 Master
1 DP Slave or MP Slave 1
2 MP Slave 2
3 MP Slave 3
4 MP Slave 4
5 MP Slave 5
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Select
Valid Values 0 to 5
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos -
IL-E -
MXIE -
ServicePanel no support

4.3.19 206Eh - Number of Active DP/MP Pumps

Description
This parameter reflects the total number of Pumps that this System consists of. All pumps that are connected to eachother are counted here, even if they have an Error present. Systems not supporting MP cannot consist of more than 2 pumps. If a pump is added or removed during runtime, this Parameter updates automatically.
Value Description
Value Description
0 Pump is a Slave (Obsolete)
1 Pump is a Single Pump
2 Pump is a Double or Multipump Master with one Slave
3 Pump is a Multipump Master with 2 Slaves
4 Pump is a Multipump Master with 3 Slaves
5 Pump is a Multipump Master with 4 Slaves
6 Pump is a Multipump Master with 5 Slaves
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
supports only the values 1, 2.
IL-E no default
supports only the values 1, 2.
MXIE no default
supports only the values 1.
ServicePanel no support

4.3.20 2070h - Pump Digital Outputs

Description
This Parameter contains all extern outputs present on the pump. This parameter is pump-specific, all the outward physical connection in the pump are represented here. In the case of a relay, the status is if it is active, not if it is open or closed (an active Normally-open relay is closed, and an active Normally-closed relay is open).
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.20.1 2070h Bit 0 - SSM Relay
Description
If the SSM Relay is active this Bit is set to 1.
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.3.20.2 2070h Bit 1 - SBM Relay
Description
If the SBM Relay is active this Bit is set to 1.
Device Support and Default Value
SupportDefault
Stratos special default
If no IF-Module with an SBM function is present, this bit is undefined.
IL-E no default
MXIE no default
ServicePanel no support

4.3.21 2072h - Pump Digital Inputs

Description
This Parameter contains all extern inputs present on the pump. This parameter is pump-specific, all the inward physical connections in the pump are represented here
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.3.21.1 2072h Bit 0 - Extern Off
Description
If the Extern Off signal at the pump is active, this bit is set to 1.
Device Support and Default Value
SupportDefault
Stratos special default
If no IF-Module with an Extern Off function is present, this bit is undefined.
IL-E no default
MXIE no default
ServicePanel no support
4.3.21.2 2072h Bit 1 - Extern Min
Description
If the Extern Min signal at the pump is active, this bit is set to 1.
Device Support and Default Value
SupportDefault
Stratos special default
If no IF-Module with an Extern Min function is present, this bit is undefined.
IL-E no support
MXIE no support
ServicePanel no support
4.3.21.3 2072h Bit 2 - Auxilary Input*
Description
This is an example of what could be realized here. In effect will all Digital Inputs be presented here.
Device Support and Default Value
SupportDefault
Stratos no support
IL-E no default
MXIE no default
ServicePanel no support

4.3.22 2076h - IF-Module

Description
This Parameter contains information about what IF-Module is inserted in the Pump.
Value Description
Value Description
0 No IF-Module Inserted
1 IF-PLR or IF-LON Inserted
2 IF-CAN Inserted
3 IF-Ext.Off/Ext.Min/SBM/0-10V Combination Inserted (Stratos only)
4 IF-BACnet MS/TP Inserted
5 IF-Modbus RTU Inserted
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Select
Valid Values 0 to 6
Error Value 0xFF
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.3.23 2077h - Actual Value Sensor Source

Description
This Parameter displays the source of the pressure for the regulation control mode.
Revision History
(1.01) Added
Value Description
Value Description
0 No Pressure Sensor or Pressure Calculation
1 Pressure Calculation (in the pump module)
2 Pump Housing Pressure Sensor (pump housing pressure correction is on, see P2316h )
3 Pump External Pressure Sensor or Other External Sensor (pump housing pressure correction is off, see P2316h ).
4 External CAN Pressure Sensor or Other CAN Sensor (pump housing pressure correction is off, see P2316h ).
5 External LON Pressure Sensor or Other Sensor (pump housing pressure correction is off, see P2316h ).
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 5
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 1
supports only the values 1,5.
IL-E 2
supports only the values 2, 3, 5.
MXIE 3
supports only the values 3, 5.
ServicePanel no support

4.4 Section Measurement

4.4.1 2083h - Speed (DP/MP)

Description
This Parameter returns the speed of the slaves in a double or multi pump system.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Speed (Master) no default
2 Speed (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Speed (Master) no default
2 Speed (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Speed (Master) no default
2 Speed (Slave 1) no default
ServicePanel does not support this Array
4.4.1.1 2083h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.4.1.2 2083h Subindex 1 - Speed (Master)
Description
This Subindex returns the speed of the Master (in a Multi Pump system or in a Double Pump system).
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 1 rpm
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.4.1.3 2083h Subindex 2 - Speed (Slave 1)
Description
This Subindex returns the speed of the Slave 1 (in a Multi Pump system) or the DP Slave (in a Double Pump system).
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 1 rpm
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.4.2 2087h - Estimated Flow (System)

Description
This Parameter returns the estimated flow in the system
Dependency
This Parameter can change if Par 2050h Bit 4 - Q not Computable changes.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 0.1 m³/h
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.4.3 2088h - Estimated Flow Range Min (System)

Description
This Parameter returns the estimated minimum limit of the total estimated flow in the system
Dependency
This Parameter can change if Par 2050h Bit 4 - Q not Computable changes.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 0.1 m³/h
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.4.4 2089h - Estimated Flow Range Max (System)

Description
This Parameter returns the estimated maximum limit of the total estimated flow in the system
Dependency
This Parameter can change if Par 2050h Bit 4 - Q not Computable changes.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 0.1 m³/h
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.4.5 208Bh - Estimated Pressure (System)

Description
This Parameter contains the calculated pressure in kPa.
Dependency
This Parameter can change if Par 2050h Bit 5 - H not Computable changes.
Dependency
This Parameter is disabled, if the Par 2001h - Control Mode (System) is set to "CONST_CONTROL (PID)".
Dependency
This Parameter is disabled, if the Par 2009h - Bus Control Mode (System) is set to "CONST_CONTROL (PID)".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.4.6 208Ch - Estimated Pressure Range Min (System)

Description
This Parameter returns the estimated minimum limit of the total estimated pressure in the system
Dependency
This Parameter can change if Par 2050h Bit 5 - H not Computable changes.
Dependency
This Parameter is disabled, if the Par 2001h - Control Mode (System) is set to "CONST_CONTROL (PID)".
Dependency
This Parameter is disabled, if the Par 2009h - Bus Control Mode (System) is set to "CONST_CONTROL (PID)".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.4.7 208Dh - Estimated Pressure Range Max (System)

Description
This Parameter returns the estimated maximum limit of the total estimated pressure in the system
Dependency
This Parameter can change if Par 2050h Bit 5 - H not Computable changes.
Dependency
This Parameter is disabled, if the Par 2001h - Control Mode (System) is set to "CONST_CONTROL (PID)".
Dependency
This Parameter is disabled, if the Par 2009h - Bus Control Mode (System) is set to "CONST_CONTROL (PID)".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.4.8 2090h - Input Power (System)

Description
This Parameter contains the (Active) Input Power of the pump System in Watts.
The resolution of the units, can be far less exact than represented here.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting 0.001 W
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.4.9 2091h - Electrical Current (System)

Description
This Parameter contains the (Apparent) Electrical Current of the System in Amperes.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting 0.001 A
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E special default
In 11-22kW this will contain error value
MXIE special default
In 11-22kW this will contain error value
ServicePanel no support

4.4.10 2092h - Voltage Level (DP/MP)

Description
This Parameter contains the actual voltage level for this double or multi pump system.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Voltage Level (Master) no default
2 Voltage Level (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Voltage Level (Master) special default
In 11-22kW this will contain error value
2 Voltage Level (Slave 1) special default
In 11-22kW this will contain error value
MXIE support the following Subindexes
0 Number of Entries no default
1 Voltage Level (Master) special default
In 11-22kW this will contain error value
2 Voltage Level (Slave 1) special default
In 11-22kW this will contain error value
ServicePanel does not support this Array
4.4.10.1 2092h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.4.10.2 2092h Subindex 1 - Voltage Level (Master)
Description
This Parameter contains the actual voltage level for the Master (in a Multi Pump system or in a Double Pump system).
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 1 V
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E special default
In 11-22kW this will contain error value
MXIE special default
In 11-22kW this will contain error value
ServicePanel no support
4.4.10.3 2092h Subindex 2 - Voltage Level (Slave 1)
Description
This Parameter contains the actual voltage level for the Slave 1 (in a Multi Pump system) or the DP Slave (in a Double Pump system).
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 1 V
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E special default
In 11-22kW this will contain error value
MXIE special default
In 11-22kW this will contain error value
ServicePanel no support

4.4.11 2093h - Input Power (DP/MP)

Description
This Parameter contains the (Active) Input Power of specific pumps in a double or multi pump system.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Input Power (Master) no default
2 Input Power (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Input Power (Master) no default
2 Input Power (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Input Power (Master) no default
2 Input Power (Slave 1) no default
ServicePanel does not support this Array
4.4.11.1 2093h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.4.11.2 2093h Subindex 1 - Input Power (Master)
Description
This Parameter contains the (Active) Input Power, in Watts of the Master (in a Multi Pump system or in a Double Pump system).
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting 0.001 W
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.4.11.3 2093h Subindex 2 - Input Power (Slave 1)
Description
This Parameter contains the (Active) Input Power, in Watts of the Slave 1 (in a Multi Pump system) or the DP Slave (in a Double Pump system).
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting 0.001 W
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.4.12 2094h - Electrical Current (DP/MP)

Description
This Parameter contains the (Apparent) Electrical Current of the double or multi pump system in Amperes.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Electrical Current (Master) no default
2 Electrical Current (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Electrical Current (Master) special default
In 11-22kW this will contain error value
2 Electrical Current (Slave 1) special default
In 11-22kW this will contain error value
MXIE support the following Subindexes
0 Number of Entries no default
1 Electrical Current (Master) special default
In 11-22kW this will contain error value
2 Electrical Current (Slave 1) special default
In 11-22kW this will contain error value
ServicePanel does not support this Array
4.4.12.1 2094h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.4.12.2 2094h Subindex 1 - Electrical Current (Master)
Description
This Parameter contains the (Apparent) Electrical Current of the Master (in a Multi Pump system or in a Double Pump system).
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting 0.001 A
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E special default
In 11-22kW this will contain error value
MXIE special default
In 11-22kW this will contain error value
ServicePanel no support
4.4.12.3 2094h Subindex 2 - Electrical Current (Slave 1)
Description
This Parameter contains the (Apparent) Electrical Current of the Slave 1 (in a Multi Pump system) or the DP Slave (in a Double Pump system).
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting 0.001 A
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E special default
In 11-22kW this will contain error value
MXIE special default
In 11-22kW this will contain error value
ServicePanel no support

4.4.13 20A0h - Medium Temperature (System)

Description
This Parameter contains the actual medium temperature in degrees Kelvin. This is measured by an internal or external sensor.
If there is no internal sensor in the pumps, the external sensor should be connected to the Master of the DP or MP System. If an external sensor is connected to the master (activated with Par 2200h - Temperature Sensor Source), this will always be used, the internal sensors will be disregarded.
Dependency
This Parameter can change source if Par 2200h - Temperature Sensor Source changes.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting 0.1 K
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no default

4.5 Section Messaging (Service and Errors)

4.5.1 20C1h - Current Warning/Error

Description
This Parameter contains the Current Error or Warning Message, if it has been Acknowledged it is cleared, and if another one happens while one is already displayed, one of them will be displayed after the next acknowledge (or self correction). In effect, this is the same error message that is displayed on the pump display. To know it this message is a Warning or Error Message Par 2052h Bit 3 - Warning Present or Par 2052h Bit 4 - Error Present must be checked.
This Parameter is reset on a power loss.
Value Description
Value Description
0 No Error
1 E01
2 E02
3 E03
n E0n
... ...
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Error Code
Valid Values 0 to 0xFF
Error Value 0x00
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.5.2 20C2h - Current Warning/Error (DP/MP)

Description
This Parameter contains the Current Warning Message for all slaves, if it has been Acknowledged it is cleared, and if another one happens while one is already displayed, one of them will be displayed after the next acknowledge. See the Par 20C1h - Current Warning/Error for a description of the values of this Parameter.
This Parameter is reset on a power loss.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Current Warning/Error (Master) no default
2 Current Warning/Error (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Current Warning/Error (Master) no default
2 Current Warning/Error (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Current Warning/Error (Master) no default
2 Current Warning/Error (Slave 1) no default
ServicePanel does not support this Array
4.5.2.1 20C2h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.5.2.2 20C2h Subindex 1 - Current Warning/Error (Master)
Description
This Subindex returns the Last Error (Master), in a Multi Pump system or in a Double Pump system.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Error Code
Valid Values 0 to 0xFF
Error Value 0x00
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.5.2.3 20C2h Subindex 2 - Current Warning/Error (Slave 1)
Description
This Subindex returns the Last Error (Slave 1), in a Multi Pump system or in a Double Pump system.
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Error Code
Valid Values 0 to 0xFF
Error Value 0x00
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.5.3 20E0h - Error History Code (Master)

Description
This Parameter Array contains the error that has happened (with history), the first object (Subindex 1) is always the last one. A maximum of 16 Errors are stored here. If an Error occurrs it is written here and the Error status bit ( Par 2052h Bit 4 - Error Present) is going high.
An Error cannot be written here without an EMCY message being sent. If any EMCY Messages were sent during the reading of these Parameters, This Parameter may have shifted, and should be read again.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Error History Code t (Master) no default
2 Error History Code t-1 (Master) no default
3 Error History Code t-2 (Master) no default
4 Error History Code t-3 (Master) no default
5 Error History Code t-4 (Master) no default
6 Error History Code t-5 (Master) no default
7 Error History Code t-6 (Master) no default
8 Error History Code t-7 (Master) no default
9 Error History Code t-8 (Master) no default
10 Error History Code t-9 (Master) no default
11 Error History Code t-10 (Master) no default
12 Error History Code t-11 (Master) no default
13 Error History Code t-12 (Master) no default
14 Error History Code t-13 (Master) no default
15 Error History Code t-14 (Master) no default
16 Error History Code t-15 (Master) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Error History Code t (Master) no default
2 Error History Code t-1 (Master) no default
3 Error History Code t-2 (Master) no default
4 Error History Code t-3 (Master) no default
5 Error History Code t-4 (Master) no default
6 Error History Code t-5 (Master) no default
7 Error History Code t-6 (Master) no default
8 Error History Code t-7 (Master) no default
9 Error History Code t-8 (Master) no default
10 Error History Code t-9 (Master) no default
11 Error History Code t-10 (Master) no default
12 Error History Code t-11 (Master) no default
13 Error History Code t-12 (Master) no default
14 Error History Code t-13 (Master) no default
15 Error History Code t-14 (Master) no default
16 Error History Code t-15 (Master) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Error History Code t (Master) no default
2 Error History Code t-1 (Master) no default
3 Error History Code t-2 (Master) no default
4 Error History Code t-3 (Master) no default
5 Error History Code t-4 (Master) no default
6 Error History Code t-5 (Master) no default
7 Error History Code t-6 (Master) no default
8 Error History Code t-7 (Master) no default
9 Error History Code t-8 (Master) no default
10 Error History Code t-9 (Master) no default
11 Error History Code t-10 (Master) no default
12 Error History Code t-11 (Master) no default
13 Error History Code t-12 (Master) no default
14 Error History Code t-13 (Master) no default
15 Error History Code t-14 (Master) no default
16 Error History Code t-15 (Master) no default
ServicePanel support the following Subindexes
0 Number of Entries no default
1 Error History Code t (Master) no default
2 Error History Code t-1 (Master) no default
3 Error History Code t-2 (Master) no default
4 Error History Code t-3 (Master) no default
5 Error History Code t-4 (Master) no default
6 Error History Code t-5 (Master) no default
7 Error History Code t-6 (Master) no default
8 Error History Code t-7 (Master) no default
9 Error History Code t-8 (Master) no default
10 Error History Code t-9 (Master) no default
11 Error History Code t-10 (Master) no default
12 Error History Code t-11 (Master) no default
13 Error History Code t-12 (Master) no default
14 Error History Code t-13 (Master) no default
15 Error History Code t-14 (Master) no default
16 Error History Code t-15 (Master) no default
4.5.3.1 20E0h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes. This number is equal to the maximum number of History Items this device can store.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 16
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.5.3.2 20E0h Subindex 1 - Error History Code t (Master)
Description
This Subindex contains the last error code.
Value Description
Value Description
01 E01
02 E02
03 E03
... etc...
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Error Code
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.5.3.3 20E0h Subindex 16 - Error History Code t-15 (Master)
Value Description
Value Description
01 E01
02 E02
03 E03
... etc...
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Error Code
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.5.4 20E1h - Error History Code (Slave 1)

Description
This Parameter Array contains the error that has happened (with history), the first object (Subindex 1) is always the last one. A maximum of 16 Errors are stored here. If an Error occurrs it is written here and the Error status bit ( Par 2052h Bit 4 - Error Present) is going high.
An Error cannot be written here without an EMCY message being sent. If any EMCY Messages were sent during the reading of these Parameters, This Parameter may have shifted, and should be read again.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Error History Code t (Slave 1) no default
2 Error History Code t-1 (Slave 1) no default
3 Error History Code t-2 (Slave 1) no default
4 Error History Code t-3 (Slave 1) no default
5 Error History Code t-4 (Slave 1) no default
6 Error History Code t-5 (Slave 1) no default
7 Error History Code t-6 (Slave 1) no default
8 Error History Code t-7 (Slave 1) no default
9 Error History Code t-8 (Slave 1) no default
10 Error History Code t-9 (Slave 1) no default
11 Error History Code t-10 (Slave 1) no default
12 Error History Code t-11 (Slave 1) no default
13 Error History Code t-12 (Slave 1) no default
14 Error History Code t-13 (Slave 1) no default
15 Error History Code t-14 (Slave 1) no default
16 Error History Code t-15 (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Error History Code t (Slave 1) no default
2 Error History Code t-1 (Slave 1) no default
3 Error History Code t-2 (Slave 1) no default
4 Error History Code t-3 (Slave 1) no default
5 Error History Code t-4 (Slave 1) no default
6 Error History Code t-5 (Slave 1) no default
7 Error History Code t-6 (Slave 1) no default
8 Error History Code t-7 (Slave 1) no default
9 Error History Code t-8 (Slave 1) no default
10 Error History Code t-9 (Slave 1) no default
11 Error History Code t-10 (Slave 1) no default
12 Error History Code t-11 (Slave 1) no default
13 Error History Code t-12 (Slave 1) no default
14 Error History Code t-13 (Slave 1) no default
15 Error History Code t-14 (Slave 1) no default
16 Error History Code t-15 (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Error History Code t (Slave 1) no default
2 Error History Code t-1 (Slave 1) no default
3 Error History Code t-2 (Slave 1) no default
4 Error History Code t-3 (Slave 1) no default
5 Error History Code t-4 (Slave 1) no default
6 Error History Code t-5 (Slave 1) no default
7 Error History Code t-6 (Slave 1) no default
8 Error History Code t-7 (Slave 1) no default
9 Error History Code t-8 (Slave 1) no default
10 Error History Code t-9 (Slave 1) no default
11 Error History Code t-10 (Slave 1) no default
12 Error History Code t-11 (Slave 1) no default
13 Error History Code t-12 (Slave 1) no default
14 Error History Code t-13 (Slave 1) no default
15 Error History Code t-14 (Slave 1) no default
16 Error History Code t-15 (Slave 1) no default
ServicePanel does not support this Array
4.5.4.1 20E1h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes. This number is equal to the maximum number of History Items this device can store.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 16
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.5.4.2 20E1h Subindex 1 - Error History Code t (Slave 1)
Description
This Subindex contains the last error code.
Value Description
Value Description
01 E01
02 E02
03 E03
... etc...
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Error Code
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.5.4.3 20E1h Subindex 16 - Error History Code t-15 (Slave 1)
Value Description
Value Description
01 E01
02 E02
03 E03
... etc...
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Error Code
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.6 Section Statistic

4.6.1 2101h - Operation Time Resettable (System)

Description
This Parameter returns the time from the System where at least one pump was running (including the time it runs in peak load), or in the case of a Single Pump, the Operation Time of the Single Pump.
If this parameter is resetted (written to 0) the Par 2104h - Parallel Operation Time Resettable (if supported by device) is also completely resetted. All other Values are not accepted.
Revision History
(1.01) Now PDO Mappable
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 1 Minutes
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access rwr
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.6.2 2103h - Operation Time Resettable

Description
This Parameter contains the individual running time for each unit of the system (peak load is included and counted only once). This means that if the Master was running alone for 5h and then together with Slave 1 for another 3h, the Master would have a total individual time of 8h (480 minutes) and Slave 1 would have 3h (180 minutes).
Revision History
(1.01) Subindexes are now PDO Mappable
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Operation Time Resettable (Master) no default
2 Operation Time Resettable (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Operation Time Resettable (Master) no default
2 Operation Time Resettable (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Operation Time Resettable (Master) no default
2 Operation Time Resettable (Slave 1) no default
ServicePanel does not support this Array
4.6.2.1 2103h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.2.2 2103h Subindex 1 - Operation Time Resettable (Master)
Description
This Parameter counts the time that the Master pump was running (including the time it runs in peak load).
This Parameter is only for the Master pump, if another pump in the same DP or MP system runs, then another value is incremented.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 1 Minutes
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access rwr
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.2.3 2103h Subindex 2 - Operation Time Resettable (Slave 1)
Description
This Parameter counts the time that the Slave 1 pump was running (including the time it runs in peak load).
This Parameter is only for the Slave 1 pump, if another pump in the same DP or MP system runs, then another value is incremented.
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Dependency
CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 1 Minutes
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access rwr
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.6.3 2104h - Parallel Operation Time Resettable

Description
This Parameter contains the simultaneous operating time (parallel operating time) of the DP or MP pump system. Subindex 1 is only incremented if exactly one pump is running. The Subindex 2 is only incremented if exactly 2 pumps are running.
If Master is exchanged, swapped with one of the Slaves or replaced by a new pump, these values are lost.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 One pump running no default
2 Two pumps running no default
IL-E support the following Subindexes
0 Number of Entries no default
1 One pump running no default
2 Two pumps running no default
MXIE support the following Subindexes
0 Number of Entries no default
1 One pump running no default
2 Two pumps running no default
ServicePanel does not support this Array
4.6.3.1 2104h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
This Subindex behaves almost exactly as the Par 206Eh - Number of Active DP/MP Pumps, the difference is that in the case of a Single Pump ( P206Eh = '1'), This Parameter is '0'.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.3.2 2104h Subindex 1 - One pump running
Description
This Parameter counts the time that one pump in the DP or MP System was running. If more than one pump were running, this parameter is not incremented.
This value is not incremented if the pump is running as a Single Pump.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 1 Minutes
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.3.3 2104h Subindex 2 - Two pumps running
Description
This Parameter counts the time that two pumps in the DP or MP System was running. If less or more than two pumps were running, this parameter is not incremented.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 1 Minutes
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.6.4 2108h - Mains Time

Description
This Parameter counts the total time that this device had mains power.
This Parameter is only for the current pump, if another pump in the same DP or MP system has power, then another value is incremented.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Mains Time (Master) no default
2 Mains Time (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Mains Time (Master) no default
2 Mains Time (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Mains Time (Master) no default
2 Mains Time (Slave 1) no default
ServicePanel does not support this Array
4.6.4.1 2108h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.4.2 2108h Subindex 1 - Mains Time (Master)
Description
This Parameter counts the total time that this device had mains power.
This Parameter is only for the Master pump, if another pump in the same DP or MP system runs, then another value is incremented.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 1 Minutes
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.4.3 2108h Subindex 2 - Mains Time (Slave 1)
Description
This Parameter counts the total time that this device had mains power.
This Parameter is only for the Slave 1 pump, if another pump in the same DP or MP system runs, then another value is incremented.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 1 Minutes
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.6.5 2109h - Uptime (System)

Description
This Parameter counts the total time that this pump had mains power, counting from last mains on.
This Parameter is only for the current pump, if another pump in the same DP or MP system has power, then another value is incremented.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile yes
Formatting 1 Minutes
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.6.6 2110h - Mains On Counter

Description
This Parameter contains the number of times the device has had the mains turned on.
If any counter would generate an overflow, it is stopped at the maximum alowable value.
Some Devices only support up to 65535 Counts.
Revision History
(1.01) Changed type, from UNSIGNED16 to UNSIGNED32.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Mains On Counter (Master) no default
2 Mains On Counter (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Mains On Counter (Master) no default
2 Mains On Counter (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Mains On Counter (Master) no default
2 Mains On Counter (Slave 1) no default
ServicePanel does not support this Array
4.6.6.1 2110h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.6.2 2110h Subindex 1 - Mains On Counter (Master)
Description
This Parameter contains the number of times the device has had the mains turned on.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.6.3 2110h Subindex 2 - Mains On Counter (Slave 1)
Description
This Parameter contains the number of times the device has had the mains turned on.
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.6.7 2111h - Pump Kick Counter

Description
This Parameter contains the number of pump kicks that has been activated. All Pump Kicks are counted disregarding from where they were initiated (the automatic ones, set with Par 2251h - Pump Kick Interval and those that are initiated with Par 2250h - Pump Kick Event).
If any counter would generate an overflow, it is stopped at the maximum alowable value.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Pump Kick Counter (Master) no default
2 Pump Kick Counter (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Pump Kick Counter (Master) no default
2 Pump Kick Counter (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Pump Kick Counter (Master) no default
2 Pump Kick Counter (Slave 1) no default
ServicePanel does not support this Array
4.6.7.1 2111h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.7.2 2111h Subindex 1 - Pump Kick Counter (Master)
Description
This Parameter contains the number of pump kicks that has been activated in the Master (in case of a DP/MP Pump) or Single Pump. This counter can be cleared by writing the Value 0, no other values are accepted.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.7.3 2111h Subindex 2 - Pump Kick Counter (Slave 1)
Description
This Parameter contains the number of pump kicks that has been activated in this specific Slave. This counter can be cleared by writing the Value 0, no other values are accepted.
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.6.8 2112h - Auto Night Mode Counter

Description
This Parameter contains the number of started automatic night mode.
If any counter would generate an overflow, it is stopped at the maximum alowable value.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Auto Night Mode Counter (Master) no default
2 Auto Night Mode Counter (Slave 1) no default
IL-E does not support this Array
MXIE does not support this Array
ServicePanel does not support this Array
4.6.8.1 2112h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support
4.6.8.2 2112h Subindex 1 - Auto Night Mode Counter (Master)
Description
This Parameter contains the number of started automatic night mode. This counter can be cleared by writing the Value 0, no other values are accepted.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support
4.6.8.3 2112h Subindex 2 - Auto Night Mode Counter (Slave 1)
Description
This Parameter contains the number of started automatic night mode. This counter can be cleared by writing the Value 0, no other values are accepted.
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFFFF
Error Value 0xFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.6.9 2113h - Consumption (System)

Description
This Parameter contains the power consumption in kWh for this System.
If any counter would generate an overflow, it is stopped at the maximum alowable value.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 0,1 kWh
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.6.10 2114h - Consumption

Description
This Parameter contains the power consumption in kWh for this pump.
If any counter would generate an overflow, it is stopped at the maximum alowable value.
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Consumption (Master) no default
2 Consumption (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Consumption (Master) no default
2 Consumption (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Consumption (Master) no default
2 Consumption (Slave 1) no default
ServicePanel does not support this Array
4.6.10.1 2114h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.10.2 2114h Subindex 1 - Consumption (Master)
Description
This Parameter contains the power consumption in kWh for this pump. This counter can be cleared by writing the Value 0, no other values are accepted.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 0,1 kWh
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.10.3 2114h Subindex 2 - Consumption (Slave 1)
Description
This Parameter contains the power consumption in kWh for this pump. This counter can be cleared by writing the Value 0, no other values are accepted.
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no, is saved on change
Formatting 0,1 kWh
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.6.11 212Fh - Q-Histogramm

Description
This Parameter contains statistical data, in order to see where the pump is working in the moment. This Parameter array can have different resolutions, but each value is always an n-th of the total range (5 values, gives each percentage a 20% share of the flow range). This Array can be reset if one of the subindexes is written to 0.
Before the data of this parameter is read, the Number of Entries must be read in order to know how many colums are present and which ranges they have.
The Par 21A7h - Max Flow must be used in order to present the maximum Flow (Qmax) in the diagram.
In the case that this pump has not yet been running, the percentages are all set to 0. In the case of a DP or MP Pump, this parameter collects data for the complete System.
The values here are resetted if the pump changes configuration (for example from Single Pump to Double Pump, or from a Multi Pump with 2 Slaves to to a Multi Pump with 3 Slaves). See Par 206Eh - Number of Active DP/MP Pumps for information when a configuration change can occur.
This Parameter is also reset on Factory Reset and if the running mode is changed (Peak mode or Main/reserve mode)
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries (n) no default
1 Q Histogram 0% - 20% no default
2 Q Histogram 20% - 40% no default
3 Q Histogram 40% - 60% no default
4 Q Histogram 60% - 80% no default
5 Q Histogram 80% - 100% no default
IL-E support the following Subindexes
0 Number of Entries (n) no default
1 Q Histogram 0% - 20% no default
2 Q Histogram 20% - 40% no default
3 Q Histogram 40% - 60% no default
4 Q Histogram 60% - 80% no default
5 Q Histogram 80% - 100% no default
MXIE support the following Subindexes
0 Number of Entries (n) no default
1 Q Histogram 0% - 20% no default
2 Q Histogram 20% - 40% no default
3 Q Histogram 40% - 60% no default
4 Q Histogram 60% - 80% no default
5 Q Histogram 80% - 100% no default
ServicePanel does not support this Array
4.6.11.1 212Fh Subindex 0 - Number of Entries (n)
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Number
Valid Values 0 to 0xFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.11.2 212Fh Subindex 1 - Q Histogram 0% - 20%
Description
This Subindex contains the percentage in which the pump was driven in this interval
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.01 Percent
Valid Values 0 to 0x7FFF
Error Value 0x7FFF
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.11.3 212Fh Subindex 2 - Q Histogram 20% - 40%
Description
This Subindex contains the percentage in which the pump was driven in this interval
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.01 Percent
Valid Values 0 to 0x7FFF
Error Value 0x7FFF
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.11.4 212Fh Subindex 3 - Q Histogram 40% - 60%
Description
This Subindex contains the percentage in which the pump was driven in this interval
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.01 Percent
Valid Values 0 to 0x7FFF
Error Value 0x7FFF
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.11.5 212Fh Subindex 4 - Q Histogram 60% - 80%
Description
This Subindex contains the percentage in which the pump was driven in this interval
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.01 Percent
Valid Values 0 to 0x7FFF
Error Value 0x7FFF
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support
4.6.11.6 212Fh Subindex 5 - Q Histogram 80% - 100%
Description
This Subindex contains the percentage in which the pump was driven in this interval
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.01 Percent
Valid Values 0 to 0x7FFF
Error Value 0x7FFF
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.7 Section Constants

4.7.1 2182h - Pump Type

Description
This Parameter contains the specific pump type. The High byte describes the Pump Family and the low byte describes the Pump with an index.
This parameter is required so that the configuration program knows what profile to load.
VDMA: part of ProductIdentifier (see Par 2180h - Manufacturer Version for the other part).
Device Support and Default Values
SubIndex Default
Stratos support the following Subindexes
0 Number of Entries no default
1 Pump Type (Master) no default
2 Pump Type (Slave 1) no default
IL-E support the following Subindexes
0 Number of Entries no default
1 Pump Type (Master) no default
2 Pump Type (Slave 1) no default
MXIE support the following Subindexes
0 Number of Entries no default
1 Pump Type (Master) no default
2 Pump Type (Slave 1) no default
ServicePanel support the following Subindexes
0 Number of Entries no default
1 Pump Type (Master) no default
4.7.1.1 2182h Subindex 0 - Number of Entries
Description
This Subindex contains the number of following subindexes.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Number
Valid Values 0 to 6
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.7.1.2 2182h Subindex 1 - Pump Type (Master)
Description
This Parameter contains the specific pump type. The High byte describes the Pump Family and the low byte describes the Pump with an index. Single or Double Pumps have the same type, they are not differentiated.
If this is changed, Par 1018h Sub 2 - Product Code must be changed as well.
Value Description
Value Description
0x0000 (0) Unknown Pump Type
0x0110 (272) Stratos 25/1-6
0x0111 (273) Stratos 30/1-6
0x0112 (274) Stratos 40/1-4
0x0113 (275) Stratos 25/1-8
0x0114 (276) Stratos 30/1-8
0x0115 (277) Stratos 25/1-10
0x0116 (278) Stratos 30/1-10
0x0117 (279) Stratos 32/1-10
0x0118 (280) Stratos 40/1-10
0x0119 (281) Stratos 50/1-10
0x011A (282) Stratos 25/1-4
0x011B (283) Stratos 30/1-4
0x0120 (288) Stratos 25/1-12
0x0121 (289) Stratos 30/1-12
0x0122 (290) Stratos 40/1-8
0x0123 (291) Stratos 50/1-8
0x0124 (292) Stratos 32/1-12
0x0130 (304) Stratos 40/1-12
0x0131 (305) Stratos 50/1-12
0x0132 (306) Stratos 50/1-9
0x0133 (307) Stratos 65/1-9
0x0140 (320) Stratos 65/1-12
0x0141 (321) Stratos 80/1-12
0x0142 (322) Stratos 100/1-12
0x2004 (8196) IP-E 40/115-0,55/2-E1-SR
0x2005 (8197) IP-E 50/115-0,75/2-E1-SR
0x2006 (8198) IP-E 32/160-1,1/2-E1-SR
0x2007 (8199) IP-E 65/115-1,5/2-E1-SR
0x2008 (8200) IP-E 80/115-2,2/2-E1-SR
0x2009 (8201) IP-E 40/150-3/2-E1-SR
0x200A (8202) IP-E 65/130-3/2-E1-SR
0x200B (8203) IP-E 50/150-4/2-E1-SR
0x200C (8204) IP-E 80/140-4/2-E1-SR
0x200D (8205) IP-E 50/140-3/2-E1-SR
0x200E (8206) IP-E 80/130-3/2-E1-SR
0x200F (8207) IP-E 40/160-4/2-E1-SR
0x2010 (8208) IP-E 65/140-4/2-E1-SR
0x2011 (8209) IP-E 32/100-0,55/2-E1-SR
0x2012 (8210) IP-E 32/110-0,75/2-E1-SR
0x2013 (8211) IP-E 40/120-1,5/2-E1-SR
0x2014 (8212) IP-E 40/130-2,2/2-E1-SR
0x2015 (8213) IP-E 50/130-2,2/2-E1-SR
0x201E (8222) IL-E 40/170-5,5/2 IE1
0x201F (8223) IL-E 50/170-7,5/2 IE1
0x2020 (8224) IL-E 65/150-5,5/2 IE1
0x2021 (8225) IL-E 80/140-7,5/2 IE1
0x2022 (8226) IL-E 40/170-5,5/2 IE2
0x2023 (8227) IL-E 50/170-7,5/2 IE2
0x2024 (8228) IL-E 65/150-5,5/2 IE2
0x2025 (8229) IL-E 80/140-7,5/2 IE2
0x2027 (8231) IL-E 125/210-5,5/4 IE1
0x202B (8235) IL-E 40/200-7,5/2 IE2
0x202C (8236) IL-E 50/160-5,5/2 IE2
0x202D (8237) IL-E 65/160-7,5/2 IE2
0x202E (8238) IL-E 80/130-5,5/2 IE2
0x202F (8239) IL-E 40/170-5,5/2 IE1
0x2030 (8240) IL-E 50/170-7,5/2 IE1
0x2031 (8241) IL-E 65/150-5,5/2 IE1
0x2032 (8242) IL-E 80/140-7,5/2 IE1
0x2033 (8243) IL-E 40/170-5,5/2 IE2
0x2034 (8244) IL-E 50/170-7,5/2 IE2
0x2035 (8245) IL-E 65/150-5,5/2 IE2
0x2036 (8246) IL-E 80/140-7,5/2 IE2
0x2037 (8247) IL-E 100/250-7,5/4 IE2
0x2038 (8248) IL-E 125/210-5,5/4 IE1
0x2039 (8249) IL-E 125/210-5,5/4 IE2
0x203A (8250) IL-E 150/190-5,5/4 IE2
0x203B (8251) IL-E 150/200-7,5/4 IE2
0x203C (8252) IL-E 80/150(143)-7,5/2-E1 Radet
0x203D (8253) IL-E 80/150-7,5/2-E1
0x203E (8254) IL-E 50/180-7,5/2 IE2
0x203F (8255) IL-E 125/220-7,5/4 IE2
0x2040 (8256) IL-E 100/220-5,5/4 IE2
0x2084 (8324) DP-E 40/115-0,55/2-E1-SR
0x2085 (8325) DP-E 50/115-0,75/2-E1-SR
0x2086 (8326) DP-E 32/160-1,1/2-E1-SR
0x2087 (8327) DP-E 65/115-1,5/2-E1-SR
0x2088 (8328) DP-E 80/115-2,2/2-E1-SR
0x2089 (8329) DP-E 40/150-3/2-E1-SR
0x208A (8330) DP-E 65/130-3/2-E1-SR
0x208B (8331) DP-E 50/150-4/2-E1-SR
0x208C (8332) DP-E 80/140-4/2-E1-SR
0x208D (8333) DP-E 50/140-3/2-E1-SR
0x208E (8334) DP-E 80/130-3/2-E1-SR
0x208F (8335) DP-E 40/160-4/2-E1-SR
0x2090 (8336) DP-E 65/140-4/2-E1-SR
0x2091 (8337) DP-E 32/100-0,55/2-E1-SR
0x2092 (8338) DP-E 32/110-0,75/2-E1-SR
0x2093 (8339) DP-E 40/120-1,5/2-E1-SR
0x2094 (8340) DP-E 40/130-2,2/2-E1-SR
0x2095 (8341) DP-E 50/130-2,2/2-E1-SR
0x20AB (8363) DL-E 40/200-7,5/2 IE2
0x20AC (8364) DL-E 50/160-5,5/2 IE2
0x20AD (8365) DL-E 65/160-7,5/2 IE2
0x20AE (8366) DL-E 80/130-5,5/2 IE2
0x20AF (8367) DL-E 40/170-5,5/2 IE1
0x20B0 (8368) DL-E 50/170-7,5/2 IE1
0x20B1 (8369) DL-E 65/150-5,5/2 IE1
0x20B2 (8370) DL-E 80/140-7,5/2 IE1
0x20B3 (8371) DL-E 40/170-5,5/2 IE2
0x20B4 (8372) DL-E 50/170-7,5/2 IE2
0x20B5 (8373) DL-E 65/150-5,5/2 IE2
0x20B6 (8374) DL-E 80/140-7,5/2 IE2
0x20B7 (8375) DL-E 100/250-7,5/4 IE2
0x20B8 (8376) DL-E 125/210-5,5/4 IE1
0x20B9 (8377) DL-E 125/210-5,5/4 IE2
0x20BA (8378) DL-E 150/190-5,5/4 IE2
0x20BB (8379) DL-E 150/200-7,5/4 IE2
0x20BD (8381) DL-E 80/150-7,5/2-E1
0x20BE (8382) DL-E 50/180-7,5/2 IE2
0x20BF (8383) DL-E 125/220-7,5/4 IE2
0x20C0 (8384) DL-E 100/220-5,5/4 IE2
0x2101 (8449) IL-E 40/220-11/2 IE2
0x2102 (8450) IL-E 50/210-11/2 IE2
0x2103 (8451) IL-E 50/220-15/2 IE2
0x2104 (8452) IL-E 65/170-11/2 IE2
0x2105 (8453) IL-E 65/200-15/2 IE2
0x2106 (8454) IL-E 65/210-18,5/2 IE2
0x2107 (8455) IL-E 65/220-22/2 IE2
0x2108 (8456) IL-E 80/160-11/2 IE2
0x2109 (8457) IL-E 80/170-15/2 IE2
0x210A (8458) IL-E 80/190-18,5/2 IE2
0x210B (8459) IL-E 80/200-22/2 IE2
0x210C (8460) IL-E 100/145-11/2 IE2
0x210D (8461) IL-E 100/150-15/2 IE2
0x210E (8462) IL-E 100/160-18,5/2 IE2
0x210F (8463) IL-E 100/165-22/2 IE2
0x2110 (8464) IL-E 100/270-11/4 IE2
0x2111 (8465) IL-E 150/220-11/4 IE2
0x2112 (8466) IL-E 150/250-15/4 IE2
0x2113 (8467) IL-E 150/260-18,5/4 IE2
0x2114 (8468) IL-E 150/270-22/4 IE2
0x2115 (8469) IL-E 200/240-15/4 IE2
0x2116 (8470) IL-E 200/250-18.5/4 IE2
0x2117 (8471) IL-E 200/260-22/4 IE2
0x2181 (8577) DL-E 40/220-11/2 IE2
0x2182 (8578) DL-E 50/210-11/2 IE2
0x2183 (8579) DL-E 50/220-15/2 IE2
0x2184 (8580) DL-E 65/170-11/2 IE2
0x2185 (8581) DL-E 65/200-15/2 IE2
0x2186 (8582) DL-E 65/210-18,5/2 IE2
0x2187 (8583) DL-E 65/220-22/2 IE2
0x2188 (8584) DL-E 80/160-11/2 IE2
0x2189 (8585) DL-E 80/170-15/2 IE2
0x218A (8586) DL-E 80/190-18,5/2 IE2
0x218B (8587) DL-E 80/200-22/2 IE2
0x218C (8588) DL-E 100/145-11/2 IE2
0x218D (8589) DL-E 100/150-15/2 IE2
0x218E (8590) DL-E 100/160-18,5/2 IE2
0x218F (8591) DL-E 100/165-22/2 IE2
0x2190 (8592) DL-E 100/270-11/4 IE2
0x2191 (8593) DL-E 150/220-11/4 IE2
0x2192 (8594) DL-E 150/250-15/4 IE2
0x2193 (8595) DL-E 150/260-18,5/4 IE2
0x2194 (8596) DL-E 150/270-22/4 IE2
0x2195 (8597) DL-E 200/240-15/4 IE2
0x2196 (8598) DL-E 200/250-18,5/4 IE2
0x2197 (8599) DL-E 200/260-22/4 IE2
0x2201 (8705) Stratos GIGA 40/1-51/4,5
0x2202 (8706) Stratos GIGA 40/1-45/3,8
0x2203 (8707) Stratos GIGA 40/1-39/3,0
0x2204 (8708) Stratos GIGA 40/1-32/2,6
0x2205 (8709) Stratos GIGA 40/1-26/1,9
0x2206 (8710) Stratos GIGA 50/1-32/2,9
0x2207 (8711) Stratos GIGA 50/1-25/2,1
0x2208 (8712) Stratos GIGA 50/1-19/1,3
0x2209 (8713) Stratos GIGA 50/1-13/0,8
0x220A (8714) Stratos GIGA 50/1-46/4,9
0x220B (8715) Stratos GIGA 50/1-43/4,2
0x220C (8716) Stratos GIGA 50/1-38/3,4
0x220D (8717) Stratos GIGA 65/1-17/1,9
0x220E (8718) Stratos GIGA 65/1-12/1,2
0x220F (8719) Stratos GIGA 65/1-8/0,6
0x2210 (8720) Stratos GIGA 65/1-27/3,2
0x2211 (8721) Stratos GIGA 65/1-23/2,3
0x2212 (8722) Stratos GIGA 65/1-45/5,7
0x2213 (8723) Stratos GIGA 65/1-39/4,7
0x2214 (8724) Stratos GIGA 65/1-34/3,7
0x2215 (8725) Stratos GIGA 80/1-22/3,7
0x2216 (8726) Stratos GIGA 80/1-16/2,3
0x2217 (8727) Stratos GIGA 80/1-38/6,4
0x2218 (8728) Stratos GIGA 80/1-32/4,9
0x2219 (8729) Stratos GIGA 100/1-18/4,1
0x221A (8730) Stratos GIGA 100/1-16/2,5
0x221B (8731) Stratos GIGA 100/1-33/6,9
0x221C (8732) Stratos GIGA 100/1-32/5,0
0x401F (16415) MVIE414-2G
0x4020 (16416) MVIE808-2G
0x4021 (16417) MVIE1605-2G
0x4022 (16418) MVIE3202-2G
0x4023 (16419) MVIE7001-2G
0x4024 (16420) HELIX VE616-2G
0x4025 (16421) HELIX VE1009-2G
0x4026 (16422) HELIX VE1604-2G
0x4027 (16423) HELIX VE2203-2G
0x4028 (16424) HELIX VE3601-2G
0x4036 (16438) DRIVE 5H5-
0x4037 (16439) DRIVE 5H6-
0x4038 (16440) DRIVE 5H5+
0x4039 (16441) DRIVE 5H6+
0x403A (16442) DRIVE 5V5-
0x403B (16443) DRIVE 5V6-
0x403C (16444) DRIVE 5V5+
0x403D (16445) DRIVE 5V6+
0x403F (16447) MVIE811-2G
0x4040 (16448) MVIE1607-2G
0x4041 (16449) MVIE3203-2G
0x4042 (16450) MVIE5202-2G
0x4043 (16451) MVIE7002/2-2G
0x4044 (16452) MVIE9501/1-2G
0x4045 (16453) HELIX VE622-2G
0x4046 (16454) HELIX VE1012-2G
0x4047 (16455) HELIX VE1606-2G
0x4048 (16456) HELIX VE2204-2G
0x4049 (16457) HELIXVE3602/2-2G
0x404A (16458) HELIX VE5201-2G
0x4056 (16470) DRIVE 7H5-
0x4057 (16471) DRIVE 7H6-
0x4058 (16472) DRIVE 7H5+
0x4059 (16473) DRIVE 7H6+
0x405A (16474) DRIVE 7V5-
0x405B (16475) DRIVE 7V6-
0x405C (16476) DRIVE 7V5+
0x405D (16477) DRIVE 7V6+
0x4101 (16641) Helix V2201
0x4102 (16642) Helix V2202
0x4103 (16643) Helix V2203
0x4104 (16644) Helix V2204
0x4105 (16645) Helix V2205
0x4106 (16646) Helix V2206
0x4107 (16647) Helix V2207
0x4108 (16648) Helix V2208
0x4109 (16649) Helix V2209
0x410A (16650) Helix V2210
0x410B (16651) Helix V2211
0x410C (16652) Helix V2212
0x410D (16653) Helix V2213
0x4120 (16672) Helix V3601/1
0x4121 (16673) Helix V3601
0x4122 (16674) Helix V3602/2
0x4123 (16675) Helix V3602/1
0x4124 (16676) Helix V3602
0x4125 (16677) Helix V3603/2
0x4126 (16678) Helix V3603/1
0x4127 (16679) Helix V3603
0x4128 (16680) Helix V3604/2
0x4129 (16681) Helix V3604
0x412A (16682) Helix V3605/2
0x412B (16683) Helix V3605
0x412C (16684) Helix V3606/2
0x412D (16685) Helix V3606
0x412E (16686) Helix V3607/2
0x412F (16687) Helix V3607
0x4130 (16688) Helix V3608/2
0x4131 (16689) Helix V3608
0x4132 (16690) Helix V3609/2
0x4133 (16691) Helix V3609
0x4134 (16692) Helix V36010/2
0x4140 (16704) Helix V5201/1
0x4141 (16705) Helix V5201
0x4142 (16706) Helix V5202/2
0x4143 (16707) Helix V5202
0x4144 (16708) Helix V5203/2
0x4145 (16709) Helix V5203
0x4146 (16710) Helix V5204/2
0x4147 (16711) Helix V5204
0x4148 (16712) Helix V5205/2
0x4149 (16713) Helix V5205
0x414A (16714) Helix V5206/2
0x414B (16715) Helix V5206
0x414C (16716) Helix V5207/2
0x414D (16717) Helix V5207
0x414E (16718) Helix V5208/2
0x414F (16719) Helix V5208
0x4150 (16720) Helix V5209/2
0x4160 (16736) Helix V1601
0x4161 (16737) Helix V1602
0x4162 (16738) Helix V1603
0x4163 (16739) Helix V1604
0x4164 (16740) Helix V1605
0x4165 (16741) Helix V1606
0x4166 (16742) Helix V1607
0x4167 (16743) Helix V1608
0x4168 (16744) Helix V1609
0x4169 (16745) Helix V1610
0x416A (16746) Helix V1611
0x416B (16747) Helix V1612
0x416C (16748) Helix V1613
0x416D (16749) Helix V1616
0x416E (16750) Helix V1619
0xC101 (49409) ServicePanel
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 0xFFFF
Error Value 0
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default
4.7.1.3 2182h Subindex 2 - Pump Type (Slave 1)
Description
This Parameter contains the specific pump type. The High byte describes the Pump Family and the low byte describes the Pump with an index. Single or Double Pumps have the same type, they are not differentiated. See Par 2182h Sub 1 - Pump Type (Master) for values.
If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile yes
Formatting Select
Valid Values 0 to 0xFFFF
Error Value 0
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.7.2 218Bh - Pump Type Name

Description
This Parameter contains the Name of this pump. It changes depending on what value is written in the Par 2180h - Manufacturer Version.
Parameter Specification
Specification
VariableType UNICODE_STRING
Volatile no
Formatting Version
Valid Values 0 to 32
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.7.3 218Ch - This Pump Function

Description
This Parameter user configureable, it contains the name of the function of the pump in the building or basement. The name must be limited to 16 UniCode characters or 32 ASCII characters.
VDMA: TechPlaceFunction
Example
'Heating'
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNICODE_STRING
Volatile no, is saved on change
Formatting Text
Valid Values 0 to 16
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.7.4 218Dh - This Pump Location/Name

Description
This Parameter user configureable, it contains the name of the place where the pump is located in the building or basement. The name must be limited to 16 UniCode characters or 32 ASCII characters.
VDMA: TechPlaceLocation
Example
'Basement C'
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNICODE_STRING
Volatile no, is saved on change
Formatting Text
Valid Values 0 to 16
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.7.5 21A0h - Min Speed (System, CONST_SPEED)

Description
The minimal possible speed of the pump in rpm.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 1 rpm
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.7.6 21A1h - Max Speed (CONST_SPEED)

Description
The max possible speed of the pump in rpm.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 1 rpm
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.7.7 21A4h - Min Pressure dp-v (VAR_DIFFPRESS)

Description
The min possible pressure in dp-v mode of the pump in kPa.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE 0xFFFF
supports only the values 0xFFFF.
ServicePanel no support

4.7.8 21A5h - Max Pressure dp-v (VAR_DIFFPRESS)

Description
The max possible pressure in dp-v mode of the pump in kPa.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE 0xFFFF
supports only the values 0xFFFF.
ServicePanel no support

4.7.9 21A7h - Max Flow

Description
The max possible flow of the pump in m³/h
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 0.1 m³/h
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE 0xFFFF
supports only the values 0xFFFF.
ServicePanel no support

4.7.10 21A8h - Min Medium Temperature

Description
This Parameter contains the min allowable medium temperature for this pump.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 0.1 K
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.7.11 21A9h - Max Medium Temperature

Description
This Parameter contains the max allowable medium temperature for this pump.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 0.1 K
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.7.12 21ABh - Max Input Power

Description
This Parameter contains the (Active) Maximum Input Power of the Pump System in Watts.
Parameter Specification
Specification
VariableType UNSIGNED32
Volatile no
Formatting 0.001 W
Valid Values 0 to 0xFFFFFFFF
Error Value 0xFFFFFFFF
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.7.13 21ACh - Min Pressure dp-c

Description
The min possible pressure in dp-c (CONST_DIFFPRESS) or p-c (CONST_PRESSURE) mode of the pump in kPa.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.7.14 21ADh - Max Pressure dp-c

Description
The max possible pressure in dp-c (CONST_DIFFPRESS) or p-c (CONST_PRESSURE) mode of the pump in kPa.
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.8 Section Configuration

4.8.1 2201h - dp-c = f(T) Regulation Tmin

Description
This Parameter sets the minimum temperature for Temperature Regulation. Since this value must always be atleast 10 degrees smaller than Par 2202h - dp-c = f(T) Regulation Tmax, the value in Par 2202h - dp-c = f(T) Regulation Tmax is always set to 10 degrees Kelvin higher than this value if it previously was lower.
Low Limit is equal to Par 21A8h - Min Medium Temperature and High Limit is equal to Par 21A9h - Max Medium Temperature.
Dependency
This Parameter can change source if Par 2200h - Temperature Sensor Source changes.
Dependency
This Parameter can change value if Par 2202h - dp-c = f(T) Regulation Tmax changes.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.1 K
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.8.2 2202h - dp-c = f(T) Regulation Tmax

Description
This Parameter sets the maximum temperature for Temperature Regulation. Since this value must always be atleast 10 degrees higher than Par 2201h - dp-c = f(T) Regulation Tmin, the value in Par 2201h - dp-c = f(T) Regulation Tmin is always set to 10 degrees Kelvin lower than this value if it previously was higher.
Low Limit is equal to Par 21A8h - Min Medium Temperature and High Limit is equal to Par 21A9h - Max Medium Temperature.
Dependency
This Parameter can change source if Par 2200h - Temperature Sensor Source changes.
Dependency
This Parameter can change value if Par 2201h - dp-c = f(T) Regulation Tmin changes.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.1 K
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.8.3 2203h - dp-c = f(T) Regulation Pmin

Description
This Parameter sets the wanted pressure at Tmin for Temperature Regulation. This value can be lower or higher than Par 2204h - dp-c = f(T) Regulation Pmax, depending on wanted function.
Default value is equal to Par 21ACh - Min Pressure dp-c.
Dependency
This Parameter can change source if Par 2200h - Temperature Sensor Source changes.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.8.4 2204h - dp-c = f(T) Regulation Pmax

Description
This Parameter sets the wanted pressure at Tmax for Temperature Regulation. This value can be lower or higher than Par 2203h - dp-c = f(T) Regulation Pmin, depending on wanted function.
Dependency
This Parameter can change source if Par 2200h - Temperature Sensor Source changes.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 0.1 kPa
Valid Values 0 to 0xFFFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.8.5 2207h - HV/AC System Error Detection

Description
This Parameter configures the pump to be used as a heating (HV) or air conditioning (AC) pump. It changes the number of Errors until an Final Error occurs.
The slave always contains the value from the master.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Heating, Ventilation (Final Error on n=6)
1 Air Conditioning (Final Error on n=1)
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE 0ff
supports only the values 0.
ServicePanel no support

4.8.6 2208h - Error Auto Reset Time

Description
This Parameter changes the auto reset time for all Errors that uses one. All other Errors remain unchanged. The auto reset time is the time at which the pump resets itself after the error has been issued. Normally this time is 5 minutes, and since the Final Error is first signalled with the 6th Error, this would take about 30 minutes. This Parameter can shorten that time.
All Slaves uses the same Value as the Master.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED16
Volatile no, is saved on change
Formatting 1 s
Valid Values 10 to 300
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE 300 s
supports only the values 300.
E001 and E011 are always fixed to 60 sec.
ServicePanel no support

4.8.7 2229h - Automatic Night Mode

Description
This Parameter sets the speed or pressure of the pump during Automatic Night Mode. It is only active if pressure regulation is chosen ( Par 2001h - Control Mode (System) equal to CONST_PRESSURE, CONST_DIFFPRESS or VAR_DIFFPRESS), if the Par 2056h Bit 0 - LON/PLR Controlled is 0 and if Par 2235h - External Setpoint Signal Type is 0.
2,3 etc... uses the min values from pressureMin, SpeedMin etc
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 disabled
1 auto
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.8.8 2232h - SBM Relay Mode

Description
This Paramater can change the behaviour of the SBM contact in the pump (it does not modify the behaviour of the I/O-Module). The trigger corresponds to the following:
With This Parameter, you can configure the SBM relays as the customer ses fit, for example: Ready for Operation or Rotating.
This Parameter affects the Master only, the Slaves behaviour will not change.
Revision History
(1.01) This Parameter has been split (see Par 2332h - SBM Relay Collective). The meaning of value 3 has been changed and value 4 has been removed. The values 3 and 4 may not be used in automatic installations containing both v1.00 and v1.01 revisions. Values 0 to 2 can be used safely across all revisions.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Relay always off
1 Pump Ready, Pull when this pump is ready (power on and no error)
2 Pump Operating, Pull when this pump is operating
3 Pump Power On, Pull when this pump has Mains Power.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 3
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 2
supports only the values 0, 1, 2.
IL-E 2
supports only the values 1, 2, 3.
MXIE 1
supports only the values 1, 2, 3.
ServicePanel no support

4.8.9 2233h - SSM Relay Mode

Description
This Paramater can change the behaviour of the SSM contact in the pump (it does not modify the behaviour of the I/O-Module). The trigger corresponds to the following:
With This Parameter, you can configure the SSM relays as the customer ses fit, for example: On Warning or on Error.
This Parameter affects the Master only, the Slaves behaviour will not change.
Revision History
(1.01) This Parameter has been split (see Par 2333h - SSM Relay Collective). Values 4 to 6 have been removed. These values may not be used in automatic installations containing both v1.00 and v1.01 revisions. Values 0 to 3 can be used safely across all revisions.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Relay always off
1 Pump Warning, Pull when this Pump has a Warning, Error or Final Error
2 Pump Error, Pull when this pump has an Error or Final Error
3 Pump Final Error, Pull when this pump has a Final Error
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 3
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 3
IL-E 3
supports only the values 3.
This value cannot be modified (read-only).
MXIE 3
supports only the values 3.
This value cannot be modified (read-only).
ServicePanel 2

4.8.10 2234h - External Setpoint Linearity

Description
This Parameter controls the Zero setpoint Mode of the External Setpoint (0-10V, 0-20mA, etc). If the setpoint is below the min-value of the pump the pump goes to the following states.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Pump Off, pump turns off at this low level and turns back on at min level, with a predefined hysteresis (default).
1 Pump Min, the pump stays at minimal value for the chosen control mode.
2 Linear, the distibution between 0 to 100% and min to max are liniar.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
supports only the values 0, 1.
IL-E no support
MXIE no support
ServicePanel no support

4.8.11 2235h - External Setpoint Signal Type

Description
This Parameter controls the activation and signal Type of the External Setpoint.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 External Setpoint Off
1 External Setpoint On (0-10 V)
2 External Setpoint On (2-10 V)
3 External Setpoint On (0-20 mA)
4 External Setpoint On (4-20 mA)
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 4
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0
supports only the values 0, 1.
It is only possible to set this Parameter to 1, if an IF-Module Stratos is inserted and the Control Mode is other than TEMP_VARIABLE. If no IF-Module is inserted or the current mode is TEMP_VARIABLE, an error will be issued (0800 0020h).
IL-E no default
MXIE no default
ServicePanel no support

4.8.12 2250h - Pump Kick Event

Description
This Parameter activates the pump kick function. If the value 1 is written, the pump (or System) briefly runs in order to avoid problem arising from standing still too long. This is only possible if the Pump has no error present.
This Parameter is default 0, if the value 1 is written, the function is executed and automatically returned to 0.
All Slaves runs simultaneously with the Master if this is activated.
If this value is written, the Pump Kick Time is NOT resetted (see Par 2251h - Pump Kick Interval).
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Event
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.8.13 2251h - Pump Kick Interval

Description
This Parameter contains how oft the pump kick is to be initiated. the value is the number of consecutive 'non running hours' between pump kicks.
If this value is written, the Pump Kick Time is resetted (it starts counting from 0).
If this Parameter is set to a time larger than 24 hours or Off, the Par 2250h - Pump Kick Event must be used regularely (at least every 24 hours). A Pump returned on warranty, with problems arising from this Parameter being set wrongly may cancel the warranty.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
1 to 127 Number of 'non running hours' between two pump kicks.
0 pump kick disabled.
Parameter Specification
Specification
VariableType SIGNED8
Volatile no, is saved on change
Formatting Hours
Valid Values 0 to 127
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no support
MXIE no support
ServicePanel no support

4.8.14 225Bh - Menu Settings Lock

Description
This Parameter locks the menu completely. By some pumps this can also be activated/deactivated by a DIP-Switch inside the pump.
Value Description
Value Description
0 Normal Access
1 Menu locked
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Bit
Valid Values 0 to 1
Error Value n/a
Access ro
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no support

4.8.15 225Dh - Display Orientation

Description
This Parameter can change the orientation of the Display. The default orientation, and the orientation rotation (90 or 180 degrees) depends on the pump type. In the case of a Pump system, all displays are rotated simultaneously.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Not rotated (product defined default)
1 Rotated (product defined)
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE special default
This value cannot be modified (read-only).
ServicePanel no support

4.8.16 225Eh - Display Unit

Description
This Parameter controls the unit displayed in the pump display.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Water Column [meters]
1 Water Column [feet]
2 Pressure [bar]
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0
supports only the values 0, 1.
IL-E 0
supports only the values 0.
This value cannot be modified (read-only).
MXIE 2
supports only the values 2.
This value cannot be modified (read-only).
ServicePanel no support

4.9 Section Double/Multi Pump

4.9.1 2315h - DP-Modus

Description
This Parameter sets the Double Pump Mode in the pump system. Parallel Operation allowes higher flow, because if one pump is not enought, the second will start. In Master-Reserve Mode, both pumps never run at the same time and if one would fail the other takes over very quickly. This Parameter can be written even if the current pump is a single pump, if this pump later becomes a master this setting becomes valid for the complete system.
Dependency
This Parameter is disabled, if the Par 2316h - Pump Housing is set to "0".
Value Description
Value Description
0 Master-Reserve (default)
1 Peak Load
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no support
ServicePanel no support

4.9.2 2320h - Pump Swap Event

Description
This Parameter is automatically resetted to zero as soon as the function has returned, it has been written as '1', and will read as a zero when the event has taken place. Writing this parameter to a '1' activates the Pump Swap Function, simultaneously the time to the next swap is reset. The next free spare pump will be chosen in the case of a MP System. Writing this Parameter to 0 is not allowed.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile yes
Formatting Event
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no support
ServicePanel no support

4.9.3 2322h - Pump Swap Interval

Description
This Parameter contains how oft the pump swap is to be initiated. the value is the number of running hours between pump swaps.
If this value is written, the Pump Swap Time is resetted (it starts counting from 0). There is no other way to reset this counter during normal operation.
This Parameter can be written even if the current pump is a single pump, if this pump later becomes a master this setting becomes valid for the complete system.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
1 to 127 Number of running hours between two pump swaps
0 automatic pump swap disabled.
Parameter Specification
Specification
VariableType SIGNED8
Volatile no, is saved on change
Formatting 1 Hours
Valid Values 0 to 127
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E special default
If value 0 is written here the Digital Input is set to trigger the Pump Swap function on rising edge.
MXIE no support
ServicePanel no support

4.9.4 2323h - Member Pump Enable

This Parameter can be written even if the current pump is a single pump, if this pump later becomes a master this setting becomes valid for the complete system.
Disable behaves like Extern Off.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Bitset Description
Bit Bit equals Zero Bit equals One
Master Disable  Master Enable 
Slave1 Disable  Slave1 Enable 
Slave2 Disable  Slave2 Enable 
Slave3 Disable  Slave3 Enable 
Slave4 Disable  Slave4 Enable 
Slave5 Disable  Slave5 Enable 
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Bitset
Valid Values 0 to 0xFF
Error Value n/a
Access rww
PDO Mappable yes
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no support
ServicePanel no support

4.9.5 2332h - SBM Relay Collective

Description
This Paramater can change the behaviour of the SBM contact in the pump (it does not modify the behaviour of the I/O-Module). The trigger corresponds to the following:
This Parameter affects the Master only, the Slaves behaviour will not change.
Revision History
(1.01) Added
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Single, Only Pulled on Master Request.
1 Collective, Pulled if Master or any Slave Requests.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 1
MXIE 0
supports only the values 0.
ServicePanel no support

4.9.6 2333h - SSM Relay Collective

Description
This Paramater can change the behaviour of the SSM contact in the pump (it does not modify the behaviour of the I/O-Module). The trigger corresponds to the following:
This Parameter affects the Master only, the Slaves behaviour will not change.
Revision History
(1.01) Added
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Single, Only Pulled on Master Request.
1 Collective, Pulled if Master or any Slave Requests.
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting Select
Valid Values 0 to 1
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos 0
IL-E 1
MXIE 0
supports only the values 0.
ServicePanel no support

4.10 Section CAN Configuration

4.10.1 2400h - CANopen Address

Description
This is the CANopen address (1-127). This Parameter only makes sense if an IF-Module-CAN is inserted. The value 0 turns the CAN bus off. To turn it on again the value should be set to the wanted address.
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting CANAddress
Valid Values 0 to 127
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

4.10.2 2403h - Auto Operational Mode

Description
the wait time before the pump goes into the Operational mode. this time starts to count down when the first foreign heartbeat is seen on the bus.
If this value is 0, the NMT Auto Operational mode is deactivated
Dependency
CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".
Value Description
Value Description
0 Auto Operational Off
1-255 Auto Operational in x Seconds
Parameter Specification
Specification
VariableType UNSIGNED8
Volatile no, is saved on change
Formatting 1 s
Valid Values 0 to 0xFF
Error Value n/a
Access rw
PDO Mappable no
Device Support and Default Value
SupportDefault
Stratos no default
IL-E no default
MXIE no default
ServicePanel no default

5    Versioning and Support

5.1  CAN Revision History

CAN Revision History
CAN Revision Parameter Change Description
1.01 2040h The effective value in dp-v is now depending on the current flow, this means that the effective value can be between 50% and 100% of the wanted setpoint.
1.01 2077h Added
1.01 2101h Now PDO Mappable
1.01 2103h Subindexes are now PDO Mappable
1.01 2110h Changed type, from UNSIGNED16 to UNSIGNED32.
1.01 2232h This Parameter has been split (see 2332). The meaning of value 3 has been changed and value 4 has been removed. The values 3 and 4 may not be used in automatic installations containing both v1.00 and v1.01 revisions. Values 0 to 2 can be used safely across all revisions.
1.01 2233h This Parameter has been split (see 2333). Values 4 to 6 have been removed. These values may not be used in automatic installations containing both v1.00 and v1.01 revisions. Values 0 to 3 can be used safely across all revisions.
1.01 2332h Added
1.01 2333h Added

5.2  CAN Revision Support

CAN Revision Support
Software Version CAN revision
Stratos (Pump Type: 01XXh)   
   v5.00 and below no support 
   v5.01-v5.04 rev 1.00 
   v5.05 and above rev 1.01 
IP-E (Pump Type: 20XXh)   
   v2.xx and below no support 
   v3.00 and above rev 1.01 
IL-E (Pump Type: 20XXh)   
   v3.xx and below no support 
   v4.00 and above rev 1.01 
MVIE (4kW and below, Pump Type: 40XXh)   
   v2.xx and below no support 
   v3.00 and above rev 1.01 
MVIE (5.5kW to 7.5kW, Pump Type: 40XXh)   
   v3.xx and below no support 
   v4.00 and above rev 1.01 
TOP-E   
   all versions no support 

5.3  Parameter Support

5.3.1 Section CANopen

Section CANopen
Parameter Stratos IL-E MXIE ServicePanel

1000h - Device Type

x x x x

1001h - Error Register

x x x x

1003h - Pre-defined Error Field

x x x x

Subindex 0 - Number of Errors

x x x x

Subindex 1 - Standard Error Field

x x x x

Subindex 8 - Standard Error Field

x x x x

1005h - COB-ID SYNC

x x x x

1008h - Manufacturer Device Name

x x x x

100Ah - Manufacturer Software Version

x x x x

1010h - Store Parameter Field

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - All Parameters

x x x x

Subindex 2 - Communication Parameters (1000h-1FFFh)

x x x x

Subindex 3 - Application Parameters (2000h-27FFh)

x x x x

1011h - Restore Default Parameters

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - All Parameters

x x x x

Subindex 2 - Communication Parameters (1000h-1FFFh)

x x x x

Subindex 3 - Application Parameters (2000h-27FFh)

x x x x

1012h - COB-ID Time Stamp

x x x x

1014h - COB-ID EMCY

x x x x

1016h - Consumer Heartbeat Time

x x x -

Subindex 0 - Number of Entries

x x x -

Subindex 1 - Consumer Heartbeat Time (I/O Module)

x x x -

1017h - Producer Heartbeat Time

x x x x

1018h - Identity Object

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - Vendor Id

x x x x

Subindex 2 - Product Code

x x x x

Subindex 3 - Revision number

x x x x

Subindex 4 - Serial number

x x x x

1200h - Server SDO Parameter 1

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - COB-ID Client -> Server

x x x x

Subindex 2 - COB-ID Server -> Client

x x x x

1400h - Receive PDO Communication Parameter 1

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - COB-ID

x x x x

Subindex 2 - Transmission Type

x x x x

1600h - Receive PDO Mapping Parameter 1

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - Mapping Entry 1

x x x x

Subindex 8 - Mapping Entry 8

x x x x

1800h - Transmit PDO Communication Parameter 1

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - COB-ID

x x x x

Subindex 2 - Transmission Type

x x x x

Subindex 3 - Inhibit Time

x x x x

Subindex 4 - Compatibility Entry

x x x x

Subindex 5 - Event Timer

x x x x

1801h - Transmit PDO Communication Parameter 2

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - COB-ID

x x x x

Subindex 2 - Transmission Type

x x x x

Subindex 3 - Inhibit Time

x x x x

Subindex 4 - Compatibility Entry

x x x x

Subindex 5 - Event Timer

x x x x

1802h - Transmit MPDO Communication Parameter 3

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - COB-ID

x x x x

Subindex 2 - Transmission Type

x x x x

Subindex 3 - Inhibit Time

x x x x

Subindex 4 - Compatibility Entry

x x x x

Subindex 5 - Event Timer

x x x x

1A00h - Transmit PDO Mapping Parameter 1

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - Mapping Entry 1

x x x x

Subindex 8 - Mapping Entry 8

x x x x

1A01h - Transmit PDO Mapping Parameter 2

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - Mapping Entry 1

x x x x

Subindex 8 - Mapping Entry 8

x x x x

1A02h - Transmit MPDO Mapping Parameter 3

x x x x

Subindex 0 - Number of Entries

x x x x

1FA0h - Object Scanner List

x x x x

Subindex 0 - Number of Entries

x x x x

Subindex 1 - Scanner Entry 1

x x x x

Subindex 8 - Scanner Entry 8

x x x x

* support may be limited, please see the specified index for more support info.

5.3.2 Section Control

Section Control
Parameter Stratos IL-E MXIE ServicePanel

2000h - Setpoint (System)

x x* x -

2001h - Control Mode (System)

0, 5, 6, 11 0, 5, 6, 12 0, 4, 12 -

2002h - Command (System)

x x x -

2008h - Bus Setpoint (System)

x x* x -

2009h - Bus Control Mode (System)

0, 5, 6, 11 0, 5, 6, 12 0, 4, 12 -

200Ah - Bus Command (System)

x x x -

* support may be limited, please see the specified index for more support info.

5.3.3 Section Status

Section Status

* support may be limited, please see the specified index for more support info.

5.3.4 Section Measurement

Section Measurement

* support may be limited, please see the specified index for more support info.

5.3.5 Section Messaging (Service and Errors)

Section Messaging (Service and Errors)

* support may be limited, please see the specified index for more support info.

5.3.6 Section Statistic

Section Statistic
Parameter Stratos IL-E MXIE ServicePanel

2101h - Operation Time Resettable (System)

x x x x

2103h - Operation Time Resettable

x x x -

Subindex 0 - Number of Entries

x x x -

Subindex 1 - Operation Time Resettable (Master)

x x x -

Subindex 2 - Operation Time Resettable (Slave 1)

x x x -

2104h - Parallel Operation Time Resettable

x x x -

Subindex 0 - Number of Entries

x x x -

Subindex 1 - One pump running

x x x -

Subindex 2 - Two pumps running

x x x -

2108h - Mains Time

x x x -

Subindex 0 - Number of Entries

x x x -

Subindex 1 - Mains Time (Master)

x x x -

Subindex 2 - Mains Time (Slave 1)

x x x -

2109h - Uptime (System)

x x x x

2110h - Mains On Counter

x x x -

Subindex 0 - Number of Entries

x x x -

Subindex 1 - Mains On Counter (Master)

x x x -

Subindex 2 - Mains On Counter (Slave 1)

x x x -

2111h - Pump Kick Counter

x x x -

Subindex 0 - Number of Entries

x x x -

Subindex 1 - Pump Kick Counter (Master)

x x x -

Subindex 2 - Pump Kick Counter (Slave 1)

x x x -

2112h - Auto Night Mode Counter

x - - -

Subindex 0 - Number of Entries

x - - -

Subindex 1 - Auto Night Mode Counter (Master)

x - - -

Subindex 2 - Auto Night Mode Counter (Slave 1)

x - - -

2113h - Consumption (System)

x x x -

2114h - Consumption

x x x -

Subindex 0 - Number of Entries

x x x -

Subindex 1 - Consumption (Master)

x x x -

Subindex 2 - Consumption (Slave 1)

x x x -

212Fh - Q-Histogramm

x x x -

Subindex 0 - Number of Entries (n)

x x x -

Subindex 1 - Q Histogram 0% - 20%

x x x -

Subindex 2 - Q Histogram 20% - 40%

x x x -

Subindex 3 - Q Histogram 40% - 60%

x x x -

Subindex 4 - Q Histogram 60% - 80%

x x x -

Subindex 5 - Q Histogram 80% - 100%

x x x -

* support may be limited, please see the specified index for more support info.

5.3.7 Section Constants

Section Constants

* support may be limited, please see the specified index for more support info.

5.3.8 Section Configuration

Section Configuration

* support may be limited, please see the specified index for more support info.

5.3.9 Section Double/Multi Pump

Section Double/Multi Pump

* support may be limited, please see the specified index for more support info.

5.3.10 Section CAN Configuration

Section CAN Configuration
Parameter Stratos IL-E MXIE ServicePanel

2400h - CANopen Address

x x x x

2403h - Auto Operational Mode

x x x x

* support may be limited, please see the specified index for more support info.





Wilo SE, Generated at 08.07.2011 08:44:30